17. RESPONSE DELAY TIME
The maximum response delay time of the complete system, calculated by considering the
scan period of the DeviceNet scanner, SL-GU1-D processing time, S-LINK system transmis-
sion time, etc., is as given below.
1. Input response delay time of complete system
= Response time of external device + Input response delay time of S-LINK system+ DeviceNet
scan time
2. Output response delay time of complete system
= DeviceNet scan time + Output response delay time of S-LINK system + Response time of
external device
where,
Input response delay time of S-LINK system
= S-LINK input unit processing time + S-LINK system transmission time + SL-GU1-D pro-
cessing time
Output response delay time of S-LINK system
= SL-GU1-D processing time + S-LINK output unit processing time + S-LINK system trans-
mission time
S-LINK input unit processing time
S-LINK output unit processing time
SL-GU1-D processing time +
S-LINK system transmission time
18. SWITCHING ON AND OFF OF POWER SUPPLY
In case a local power supply is used for the connected devices and the S-LINK units, switch
RQ WKH ORFDO SRZHU VXSSO\ ¿UVW
In case the booster (SL-BS1A), is used with a local power supply, switch on the supply of
SL-BS1A, either earlier or at the same time as the supply of SL-GU1-D.
Item
32 points
64 points
96 points
128 points
Time (Max.)
0.6ms
2.0ms
6.3ms
7.7ms
10.0ms
12.1ms