OpenAir™ GCA Series Spring Return 160 lb-in Electronic Damper Actuator

Specifications

Ambient
Conditions
Agency
Certification
Conformity
Power
Supply
Frequency
Power Consumption
Control Signal
Input Signal
(Y–G0)
voltage input
input resistance
Feedback
Signal
Position output signal
(U-G0)
voltage output
maximum output
current
Function
Equipment rating
Siemens Industry, Inc.
Ambient temperature
operation
storage and transport
Ambient humidity (non-condensing)
Electromagnetic compatibility (EMC)
Immunity for all models, except GCA132.xx
Immunity for GCA132.xx
Emissions for all models
GCA16x
24 Vac ± 20%
24 Vdc ± 10%
50/60 Hz
running
7 VA/5W
holding
5 VA/3W
GCA16x
0 to 10 Vdc
(max. 35 Vdc)
>100K ohms
GCA16x
0 to 10 Vdc
±1 mA
Running/spring return torque
Operating with 24 Vac
Maximum torque
Runtime for 90°
operating with motor
closing (on power loss) with spring return 15 seconds typical
NOTE: At -25°F, spring return is 142 lb-in (16 Nm
-25°F to 130°F (-32°C to 55°C)
-40°F to 158°F (-40°C to 70°C)
95% rh
2004/108/EC
EN61000-6-2
EN61000-6-1
EN61000-6-3
GCA15x
GCA13x
24 Vac ± 20%
24 Vac± 20%
24 Vdc ± 10%
24 Vdc ± 10%
50/60 Hz
50/60 Hz
7 VA/5W
7 VA/5W
5 VA/3W
5 VA/3W
GCA15x
GCA13x
0 to 10 Vdc or
Floating
2 to 10 Vdc
(max. 35 Vdc)
>100K ohms
GCA15x
GCA13x
0 to 10 Vdc
0 to 1000 ohms
<10 Ma
(GCA 132x only)
Load <1W
+1 mA,
-.5 mA
160 lb-in (18 Nm)
<360 lb-in (40 Nm)
90 sec
Class 2, in accordance with UL/CSA
Technical Instructions
Document No. 155-173P25
January 26, 2011
UL listed to UL60730
(to replace UL873)
cUL certified to Canadian Standard
C22.2 No. 24-93
GCA12x
GCA22x
24 Vac ±
120 Vac ±
20%
24 Vdc ±
10%
50/60 Hz
50/60 Hz
7 VA/5W
8 VA
5 VA/3W
6 VA
GCA12x
GCA22x
2-Position
2-Position
GCA12X
GCA22x
).
10%