YASKAWA 1000 Series Installation Manual page 24

Ac drive, option, analog input
Hide thumbs Also See for 1000 Series:

Advertisement

6 Related Parameters
Parameter Table
No.
(Addr.
Name
Hex)
F2-01
Analog Input Option Operation
(38F)
Selection
F2-02
Option Input Terminal Gain
(368)
F2-03
Option Input Terminal Bias
(369)
H3-02
Terminal A1 Function Selection
(434)
H3-03
Terminal A1 Gain Setting
(411)
H3-04
Terminal A1 Bias Setting
(412)
H3-06
Terminal A3 Function Selection
(414)
H3-07
Terminal A3 Gain Setting
(415)
H3-08
Terminal A3 Bias Setting
(416)
H3-10
Terminal A2 Function Selection
(418)
H3-11
Terminal A2 Gain Setting
(419)
H3-12
Terminal A2 Bias Setting
(41A)
24
Table 5 Related Parameters
0: Separate channels. Option input terminals V1, V2,
and V3 replace drive input terminals A1, A2, and
A3.
1: Combined. Input signals to terminals V1, V2, and
V3 are added together to create the frequency
reference.
When F2-01 = 0, Frequency Reference Selection 1
(b1-01) must be assigned to 1 (analog input
terminals).
Sets the gain for the analog reference as a percentage
of the maximum output frequency.
Sets the bias for the analog reference as a percentage
of the maximum output frequency.
Sets the function of terminal A1.
Sets the level of the input value selected in H3-02
when 10 V is input at terminal A1.
Sets the level of the input value selected in H3-02
when 0 V is input at terminal A1.
Sets the function of terminal A3.
Sets the level of the input value selected in H3-02
when 10 V is input at terminal A3.
Sets the level of the input value selected in H3-06
when 0 V s input at terminal A3.
Sets the function of terminal A2.
Sets the level of the input value selected in H3-10
when 10 V (20 mA) is input at terminal A2.
Sets the level of the input value selected in H3-10
when 0 V (0 or 4 mA) is input at terminal A2.
YASKAWA ELECTRIC TOBP C730600 38C 1000-Series Option AI-A3 Installation Manual
Description
Values
Default: 0
Range: 0, 1
Default: 100.0%
Min: -999.9
Max: 999.9
Default: 0.0%
Min: -999.9
Max: 999.9
Default: 0
Range: 0 to 31
Default: 100.0%
Min: -999.9
Max: 999.9
Default: 0.0%
Min: -999.9
Max: 999.9
Default: 2
Range: 0 to 31
Default: 100.0%
Min: -999.9
Max: 999.9
Default: 0.0%
Min: -999.9
Max: 999.9
Default: 0
Range: 0 to 31
Default: 100.0%
Min: -999.9
Max: 999.9
Default: 0.0%
Min: -999.9
Max: 999.9