3-phase condensing unit wiring diagram
PHASE MONITOR
LPC
20
(Danfoss MTZ36-3AV) MOP = 25; MCA = 15.7
(Danfoss MTZ44-3AV) MOP = 30; MCA = 19.9
NOTE: MAKE CONNECTIONS
AT CONTACTOR LUGS
HPC
CONDENSER
FAN
MOTOR
208-230V/3/60Hz
CIRCUIT BREAKER (by others)
25A for MTZ36-3AV
30A for MTZ44-3AV
C
CC
T2
T1
T3
COMPRESSOR
HC_1810R/N, HC_2110R/N, HM_1810R/N, HM_2110R/N
HIGH LIMIT 80F
HC
PTC
CCH
AR