Refrigeration - Scotsman F0822 User And Installation Manual

Modular flaked & nugget ice machines
Table of Contents

Advertisement

N0622L, F0822L, N0922L, F1222L, N1322L, F1522L
Remote Low Side User's Manual

Refrigeration

BTUH Capacity Requirements
Model
N0622L or F0822L
N0922L, F1222L
N1322L
Condensing Units
Model
N0622L or F0822L
N0922L or F1222L
N1322L
Remote low side models require connection to
a dedicated condensing unit or a rack system.
Recommended Tubing from Head to Condensing
Unit
Suction Line: 5/8" OD
Liquid Line: 3/8" OD
Distance limits:
Maximum distance between dedicated
condensing unit and head: 75 feet.
Condensing Unit Elevation over Ice Making
Section: 35 feet.
Note: Elevations greater than 20 feet require
installation of a suction line trap at the 10 foot
mark.
Ice Making Section
Elevation over Condensing Unit: 15 feet.
Line Routing:
Allowed: One rise after a drop.
Allowed: One drop after a rise.
Not Allowed: More than one rise after a drop
Not Allowed: More than one drop after a rise
BTUH
4,000
5,000
7,200
Use Condensing Unit
NME654-RHS-A/C
NME954-RHS-A/C
None - rack only
July 2009
Page 8
Roof Attachment
Install and attach the remote condensing unit to the
roof of the building, using the methods and
practices of construction that conform to the local
building codes, including having a roofing
contractor secure the condenser to the roof.
Refrigeration Installation:
Connections
The liquid and suction fittings on the back of the
cabinet are stubs. The liquid line size is 3/8" OD.
The suction line size is 5/8" OD.
1. Recover holding charge
2. Cut the stubs off.
3. Braze line set tubing to each fitting. Sweep with
dry nitrogen while brazing.
4. Dedicated condensing unit: Evacuate complete
system to 50 microns.
5. Open the ball valves.
Rack: The skills of a refrigeration technician are
required to connect the ice machine to the
building's refrigeration system.
Notes:
R-404A models: 1.5 ounces of R-404A
refrigerant is in the system as a holding
charge.
Be sure the liquid connection is NOT in
series with another liquid line valve.
Local Codes must be observed.
Dedicated condensing unit: Add refrigerant charge.
Recommended starting field charge:
N0622L or F0822L: 8 lb R-404A
N0922L or F1222L: 8 lb R-404A
N1322L: n/a - rack only