Vertical Sidewall Applications - Vermont Castings DVRS3 Installation Instructions & Homeowner's Manual

Vermont castings rear vented direct vent installation instructions & home owner's manual
Table of Contents

Advertisement

Maximum Length
12" (294mm)
#8
SCREWS(2)
ADJUSTABLE ZERO
CLEARANCE SLEEVE
STEP 3
Measure from fireplace collar to face of outside wall (add 2"
for vent pipe overlap. Mark pipes and cut to length. It is very
important that the two pipes are flush with the outside wall
once the fireplace is in its final location. Fig. 13.
STEP 4
Slip 4" and 7" pipes onto respective flue collars. Make sure
to fix to the fireplace collar the 4" pipe with three (3) screws
before fixing the 7" pipe on the 7" collar. Both pipes must
be on a level plane. Fig. 13.
STEP 5
Guide the vent termination 4" collar into the 4" pipe then the
7" collar into the 7" pipe. Do not force the venting into
position. If the pipes do not line up with the termination
collars, disassemble pipes and reattach to the fireplace
collar. (Fig. 13)
STEP 6
Secure fireplace to floor through floor holes and adjustable
frame drywall strip (nailing flange) to frame. (See Framing
& Finishing Section)
#8
SCREWS(2)
ADJUSTABLE
ZERO CLEARANCE
SLEEVE
#8
SCREWS(2)
FIRESTOP
Fig. 12
Fig. 13

VERTICAL SIDEWALL APPLICATIONS

Vent Starter Kit 7DVSK, plus Transition Elbow
7DVRT90 must be used in Vertical Sidewall
installations.
inside the 7" pipe coming off the 7DVRT90
transition elbow.
Since it is very important that the venting system
maintain its balance between the combustion air intake
and the flue gas exhaust, certain limitations as to vent
configurations apply and must be strictly adhered to.
The graph showing the relationship between vertical and
horizontal side wall venting will help to determine the
various vent lengths allowable. Fig. 19.
Minimum clearance between vent pipes and
combustible materials is one (1") inch (25
mm) on top, bottom and sides unless
otherwise noted.
When vent termination exits through
foundation less than 20" below siding outcrop,
the vent pipe must flush up with the siding. A
7DVSS must also be used.
It is always best to locate the fireplace in such a way that
minimizes the number of offsets and horizontal vent
length.
The horizontal vent run refers to the total
length of vent pipe from the flue collar of the
fireplace to the face of the outer wall.
Horizontal plane means no vertical rise
exists on this portion of the vent assembly.
For some installations, it may be desireable
to have some amount of the horizontal vent
run immediately after the fireplace. A verti-
cal rise must be
anywhere in the vent system, to meet the
perimeters identified in the venting graph.
The maximum horizontal vent run is 20 feet (6100mm)
when the vertical vent rise is 7.5 feet (2286mm). Fig. 14
7.5'
90"
(2286mm)
- 10 -
The 4" pipe must be centred
used but can be located
MAXIMUM
20ft.
(6100mm)
48"
(1220mm)
12"
15ft.
(305
(4572
TERMINATION
mm)
mm)
Vertical Dimension
8ft. minimum when
horizontal run is
20 ft.
7DVT90
ELBOW
SIDE VIEW
VENT
Fig. 14

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

DvrsrDvrsl

Table of Contents