Carrier WeatherExpert 48LC Series Service And Maintenance Instructions page 41

Single package rooftop gas heating/electric cooling unit
Table of Contents

Advertisement

MENU
PARAMETER
INSTALL
UNITS DEG
EQUIPMENT
AUX2 IN
FAN SPEED
SYSTEM
SETUP
FAN CFM
AUX1 OUT
OCC
FACTORY DEFAULT
MA LO SET
FREEZE POS
CO2 ZERO
CO2 SPAN
STG3 DLY
SD DMPR POS
ADVANCED
SETUP
DA LO ALM
DA HI ALM
DCVCAL ENA
MAT T CAL
OAS T CAL
OA H CAL
Table 19 — W7220 Menu Structure* (cont)
PARAMETER
PARAMETER
DEFAULT
RANGE AND
VALUE
INCREMENT
01/01/10
N/A
°F
°F or °C
CONV
CONV
or
HP
Shutdown (SD)
Heat (W1)
W
HP(O)
HP(B)
2 speed
1 speed/2 speed
100 to 15000 cfm;
5000 cfm
increment by 100
NONE
ERV
NONE
EXH2
SYS
INPUT
INPUT or ALWAYS
NO
NO or YES
35°F to 65°F
45°F (7°C)
(2°C to 18°C);
Increment by 1°F
CLO
CLO or MIN
0 to 500 ppm;
0ppm
Increment by 10
1000 to 3000 ppm;
2000ppm
Increment by 50
0 min, 5 min,
15 min, then 15 min
2.0h
intervals. Up to
4 hrs or OFF
CLO
CLO or OPN
NONE
35°F to 65°F
45°F (7°C)
(2°C to 18°C);
Increment by 5°F
NONE
70°F to 180°F
80°F (27°C)
(21°C to 82°C);
Increment by 5°F
MAN (manual)
MAN
AUTO
0.0°F
± 2.5°F
0.0°F
± 2.5°F
0% RH
±10% RH
41
EXPANDED PARAMETER NAME
Display order = MM/DD/YY
Setting order = DD, MM, then YY.
Sets economizer controller in degrees Fahrenheit or Celsius
CONV = conventional;
HP O/B = Enable Heat Pump mode. Use AUX2 I for Heat Pump
input from thermostat or controller.
In CONV mode:
SD = Enables configuration of shutdown (default);
W = Informs controller that system is in heating mode.
In HP O/B mode:
HP(O) = energize heat pump on Cool (default);
HP(B) = energize heat pump on heat.
Sets the economizer controller for operation of 1 speed or 2
speed supply fan. The controller does not control the fan, but
positions the OA and RA dampers to heating or cooling mode.
UNIT DESIGN AIRFLOW (CFM)
Enter only if using DCVCAL ENA = AUTO
This is the capacity of the RTU. The value is found on the
nameplate label for the specific unit.
Select OUTPUT for AUX1 O relay
• NONE = not configured (output is not used)
• ERV = Energy Recovery Ventilator
• EXH2 = second damper position 24 vac out for second exhaust
fan
• SYS = use output as an alarm signal
OCCUPIED MODE BY EXTERNAL SIGNAL
When using a setback thermostat with occupancy out (24 vac),
the 24 vac is input "INPUT" to the OCC terminal. If no occupancy
output from the thermostat, then change program to "ALWAYS"
OR add a jumper from terminal R to OCC terminal.
Resets all set points to factory defaults when set to YES. LCD
will briefly flash YES and change to NO but all parameters will
change to the factory default values.
SUPPLY AIR TEMPERATURE LOW LIMIT
Temperature to activate Freeze Protection (close damper or
modulate to MIN POS if temp falls below set value).
FREEZE PROTECTION DAMPER POSITION
Damper position when freeze protection is active (closed or MIN
POS).
CO
ppm level to match CO
2
CO
ppm span to match CO
2
output would be 500 CO
zero and 1000 CO
2
COOLING STAGE 3 DELAY
Delay after stage 2 cool has been active. Turns on second stage
of cooling when economizer is first stage call and mechanical
cooling is second stage call. Allows three stages of cooling, 1
economizer and 2 mechanical.
OFF = no Stage 3 cooling
Indicates shutdown signal from space thermostat or unitary
controller. When controller receives 24 vac input on the SD
terminal in conventional mode, the OA damper will open if
programmed for OPN and OA damper will close if programmed
for CLO. All other controls, e.g., fans, etc. will shut off.
Used for alarm for when the DA air temperature is too low. Set
lower range of alarm, below this temperature the alarm will show
on the display.
Used for alarm for when the DA air temperature is too high. Sets
upper range of alarm; above this temperature, the alarm will
show on the display.
Turns on the DCV automatic control of the dampers. Resets
ventilation based on the RA, OA, and MA sensor conditions.
Requires all (RA, OA, MA, CO
This operation is not operable with a 2-speed fan unit.
SUPPLY AIR TEMPERATURE CALIBRATION
Allows for the operator to adjust for an out of calibration
temperature sensor.
OUTSIDE AIR TEMPERATURE CALIBRATION
Allows for the operator to adjust for an out of calibration
temperature sensor.
OUTSIDE AIR HUMIDITY CALIBRATION
Allows for operator to adjust for an out of calibration humidity
sensor.
Notes
††
sensor start level.
2
sensor; e.g.: 500-1500 sensor
2
span.
2
) sensors.
2

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents