TERMINAL LABEL
INPUTS
RT, C
SS
FS, T1
W
RS
LS
CS
OUTPUTS
L1, CM
IFO
GV
Table 10 — Orifice Sizes
ORIFICE
CARRIER
DRILL SIZE
PART NUMBER
LH32RF129
#30
LH32RF125
1/8
LH32RF120
#31
LH32RF116
#32
LH32RF113
#33
LH32RF111
#34
LH32RF110
#35
LH32RF105
#36
LH32RF104
#37
LH32RF102
#38
LH32RF103
#39
LH32RF098
#40
LH32RF096
#41
LH32RF094
#42
LH32RF089
#43
LH32RF086
#44
LH32RF082
#45
LH32RF080
#46
LH32RF079
#47
LH32RF076
#48
LH32RF073
#49
LH32RF070
#50
LH32RF067
#51
LH32RF065
#52
LH32RF060
#53
LH32RF055
#54
LH32RF052
#55
LH32RF047
#56
LH32RF043
#57
LH32RF042
#58
Table 9 — IGC Connections
POINT DESCRIPTION
Input power from TRAN 1
Speed sensor
Flame sensor
Heat stage 1
Rollout switch
Limit switch
Centrifugal switch (not used)
Induced draft combustion motor
Indoor fan
Gas valve (heat stage 1)
DRILL
DIA. (in.)
0.1285
0.1250
0.1200
0.1160
0.1130
0.1110
0.1100
0.1065
0.1040
0.1015
0.0995
0.0980
0.0960
0.0935
0.0890
0.0860
0.0820
0.0810
0.0785
0.0760
0.0730
0.0700
0.0670
0.0635
0.0595
0.0550
0.0520
0.0465
0.0430
0.0420
SENSOR LOCATION
control box
gas section
gas section
LCTB
gas section
fan section
gas section
control box
gas section
28
CONNECTION
TYPE OF I/O
PIN NUMBER
24 VAC
analog input
J1, 1-3
switch input
24 VAC
J2, 2
switch input
J2, 5-6
switch input
J2, 7-8
switch input
J2, 9-10
line VAC
relay
J2, 1
relay
J2, 11-12