Cable and wire length guidelines
The following table defines cable length guidelines for the various wire sizes that may be used for
wiring low-voltage (<30 V) input and outputs.
Table 4: Cable length guidelines
Guideline
Wire size/gauge and type Maximum cable
A
1.0 mm (18 AWG) stranded
copper
0.8 mm (20 AWG) stranded
copper
0.6 mm (22 AWG) stranded
copper
0.5 mm (24 AWG) stranded
copper
B
1.0 mm (18 AWG) stranded
copper
0.8 mm (20 AWG) stranded
copper
0.6 mm (22 AWG) stranded
copper
0.5 mm (24 AWG) stranded
copper
C
See Figure 8 to select wire
size/gauge. Use stranded
copper wire.
Maximum cable length versus load current
Use the following figure to estimate the maximum cable length relative to the wire size and the
load current (in mA) when wiring inputs and outputs.
Note: The following information applies to low-voltage (<30 V) inputs and outputs only.
16
FX-PCX2721 Expansion Input/Output Module Installation Instructions
Assumptions
length and type
457 m (1,500 ft)
100 mV maximum voltage drop
twisted wire
Depending on cable and the
297 m (975 ft)
connected input or output device,
twisted wire
you may have to define an offset
183 m (600 ft)
in the setup software for the input
twisted wire
or output point.
107 m (350 ft)
twisted wire
229 m (750 ft)
100 mV maximum voltage drop
twisted wire
Depending on cable and the
137 m (450 ft)
connected input or output device,
twisted wire
you may have to define an offset
91 m (300 ft)
in the setup software for the input
twisted wire
or output point.
61 m (200 ft)
twisted wire
See Figure 8 to
N/A
determine cable
length. Use twisted
wire cable.