Air Quality Hazard - Dyna-Glo Delux RMC-FA150NGDGD Operating Instructions & Parts Manual

Natural gas construction heater
Hide thumbs Also See for Delux RMC-FA150NGDGD:
Table of Contents

Advertisement

Dyna-Glo Delux Operating Instructions and Parts Manual
Dyna-Glo
Construction Heater
For either indoor or outdoor use. Adequate ventilation shall be provided in accordance with OSHA 29 CFR
1926.154, Safety Requirements for Temporary and Portable Space Heating Devices and Equipment ANSI A10.10,
ANSI 223.1 / NFPA 54, Liquified Petroleum Gas Code, NFPA 58 or the National Gas and Propane Installation Code,
CAN B149.1 as appropriate.
Do not use this heater for heating human living quarters.
Use of direct-fired heaters in the construction environment can result in exposure to levels of CO, CO
NO
considered to be hazardous to health and potentially life threatening.
2
Do not use in unventilated areas
Know the signs of CO and CO
▫ Headaches, stinging eyes
▫ Dizziness, disorientation
▫ Difficulty breathing, feels of being suffocated
Proper ventilation air exchange (OSHA 29 CFR 1926.57) to support combustion and maintain acceptable air
quality shall be provided in accordance with OSHA 29 CFR Part 1926.154, ANSI A10.10 Safety Requirements
for Temporary and Portable Space Heating Devices and Equipment used in the Construction Industry or the
Natural Gas and Propane Installation Codes CSA B149.1
▫ Periodically monitor levels of CO, CO
start of the shift and after 4 hours.
▫ Provide ventilation air exchange, either natural or mechanical, as required to maintain acceptable indoor
air quality
USA 8-Hr Time weighted average
(OSHA 29 CFR 1926.55 App A)
CO
CO
2
NO
2
USA – Ceiling Limit
(Short Term Exposure Limit = 15 minutes)
CO
CO
2
NO
2
• Ensure that the flow of combustion and ventilation air exchange cannot become obstructed.
• As the building 'tightens up' during the construction phases ventilation may need to be increased.
For Technical Support or Troubleshooting, Call: 1-877-447-4768, 8:30 am - 4:30 pm CST
Delux Natural Gas
®
WARNING
: NOT FOR USE WITH DUCT WORK.

Air Quality Hazard

poisoning
2
and NO
2
50 ppm
5000 ppm
5 ppm
WARNING
existing at the construction site – at the minimum at the
2
Canada 8-hr time weighted average
WorkSafe BC OHS Guidelines Part 5.1
and Ontario Workplaces Reg 833
Canada STEL (15 minutes Reg 833/1 hour WSBC)
WorkSafe BC OHS Guidelines Part 5.1 and Ontario
Workplaces Reg 833
9
RMC-FA150NGDGD
25 ppm
5000 ppm
3 ppm (Reg 833)
100 ppm
15000 ppm (WSBC)
30000 ppm (Reg 833)
1.0 ppm (WorkSafeBC)
5.0 ppm (Reg 833)
www.ghpgroupinc.com
, and
2