7-20
Bosch Rexroth AG | Electric Drives and Controls
Interfaces
7.2.4

Pin Assignment

7.2.5

Cable

Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com

Fig. 7-29: 9-pin D-SUB female connector strip

Connector in the small operator terminal: 9-pin D-SUB female connec-
tor strip
Pin Designation Function
1
nc
Not Connected
2
nc
Not Connected
3
RxD/TxD-P
Received Data / Transmitted Data Plus
4
CNTR-P
Repeater Control Signal Plus
5
DGND
Data Transmission Potential
6
VP
Supply Voltage of Terminators Plus
7
nc
Not Connected
8
RxD/TxD-N
Received Data / Transmitted Data Minus
9
CNTR-N
Repeater Control Signal Minus

Fig. 7-30: Pin assignment PROFIBUS DP

The D-SUB connector strips must be shielded sufficiently. See chapter
"Shielding D-SUB Connectors" on page 7-22.
Any PROFIBUS DP-approved cables specified in the EN 50170 as ca-
ble type A can be used.
Impedance
Capacity
Loop resistance
Wire gauge
Rexroth IndraControl VCP 05 | R911299726 / 02
136 to 165 Ohm
< 30 pf/m
110 Ohm/km
0.64 mm