Ahu control kit
Table of Contents

Advertisement

• Coil Register
Address
No.
Hexadecimal
Decimal
1
0x0000
0
2
0x0001
1
3
0x0002
2
• Discrete Register
Address
No.
Hexadecimal
Decimal
1
0x0000
0
2
0x0001
1
3
0x0002
2
9
0x0008
8
10
0x0009
9
11
0x000A
10
12
0x000B
11
13
0x000C
12
14
0x000D
13
17
0x0010
16
18
0x0011
17
19
0x0012
18
20
0x0013
19
21
0x0014
20
22
0x0015
21
23
0x0016
22
24
0x0017
23
25
0x0018
24
26
0x0019
25
27
0x001A
26
28
0x001B
27
29
0x001C
28
30
0x001D
29
33
0x0020
32
34
0x0021
33
35
0x0022
34
36
0x0023
35
39
0x0026
38
40
0x0027
39
41
0x0028
40
42
0x0029
41
43
0x002A
42
44
0x002B
43
Register
High
1
Operation Setting
2
Automatic return air (additional operation)
3
Humidification function (additional operation)
Register
High
10001
Return air fan operating status
10002
Supply air fan operating status
10003
Preheating heater status
10009
Alarm Level1
10010
Alarm Level2
10011
Alarm Level3
10012
Smoke detection
10013
Filter Replacement
10014
Filter Not Replaced Alarm
10017
Return Air FAN 1 Operating Status
10018
Return Air FAN 2 Operating Status
10019
Return Air FAN 3 Operating Status
10020
Return Air FAN 4 Operating Status
10021
Return Air FAN 5 Operating Status
10022
Return Air FAN 6 Operating Status
10023
10024
10025
Supply Air FAN 1 Operating Status
10026
Supply Air FAN 2 Operating Status
10027
Supply Air FAN 3 Operating Status
10028
Supply Air FAN 4 Operating Status
10029
Supply Air FAN 5 Operating Status
10030
Supply Air FAN 6 Operating Status
10033
Outdoor Unit 1 Operating Status
10034
Outdoor Unit 2 Operating Status
10035
Outdoor Unit 3 Operating Status
10036
Outdoor Unit 4 Operating Status
10039
10040
10041
Outdoor Unit 1 Defrost Status
10042
Outdoor Unit 2 Defrost Status
10043
Outdoor Unit 3 Defrost Status
10044
Outdoor Unit 4 Defrost Status
Data Bit
Low
Data Bit
Low
Reserved
Reserved
Reserved
Reserved
HMI SETTINGS
41
Notes
0: Off / 1: On
0: Off /
1: Automatic return air
0: Off / 1: Humidification
Notes
0:Off, 1:On
0:Off, 1:On
0:Off, 1:On
0:Normal, 1:Alarm
0:Normal, 1:Alarm
0:Normal, 1:Alarm
0:Normal, 1:Alarm
0:Normal, 1:Alarm
Occurs 300 hours after the
filter replacement alarm
0:Off, 1:On
0:Off, 1:On
0:Off, 1:On
0:Off, 1:On
0:Off, 1:On
0:Off, 1:On
0:Off, 1:On
0:Off, 1:On
0:Off, 1:On
0:Off, 1:On
0:Off, 1:On
0:Off, 1:On
0:Off, 1:On
0:Off, 1:On
0:Off, 1:On
0:Off, 1:On
0:No function, 1:Defrost
0:No function, 1:Defrost
0:No function, 1:Defrost
0:No function, 1:Defrost