- Filter Differential Sensor
Item
Filter Differential
Sensor
Ex: Filter Differential Sensor (voltage type) Connection
CAUTION
!
• Improper wiring of the sensor can damage the AHU CONTROL KIT. Make sure to check for
any incorrect wiring before turning the power on.
1. For more information on the installation of a filter differential sensor, refer to the Manual
that came with the sensor.
2. Make sure to finish all the sensor wires with a flexible tube.
3. The setting for the filter differential pressure can be changed in the setting section of the
HMI.
Specification
- Power: AC 24 V
- Output signal: DC 0~10 V
- Range: 0~1 000 Pa
AC 24 V(G)
Ground (G0)
AC 24 V(G)
<Terminal block>
<UI module>
AHU SENSOR CONNECTION
Ground (G0)
DC 0~10 V(Y, Feedback)
23