Planning The Floor Layout; Removing And Installing The Outriggers (Side Stabilizers) - IBM Power Systems 7953-94X Installing

Rack and features
Hide thumbs Also See for Power Systems 7953-94X:
Table of Contents

Advertisement

Table 2. IBM PureFlex System 42U Rack and Expansion Rack weights
Model
Description
7953-94X and
With side panels, with outriggers
7953-94Y
7953-94X and
With side panels, without outriggers
7953-94Y
7953-94X and
Without side panels, with outriggers
7953-94Y
7953-94X and
Without side panels, without outriggers
7953-94Y

Planning the floor layout

Learn more about how to plan your floor layout for this rack.
For planning purposes, use the floor layout that is shown in the following illustration as a guide for
cutting holes in the floor tiles to run cables for the devices in the rack cabinet.
The circles in the illustration represent the area where the casters and leveling feet might touch the
ground. Ensure that there are no holes in the floor tiles that are too close to these circles.
600 mm
198.74 mm
458.37 mm
Front of Rack
Figure 3. Floor layout for cutting holes in the floor tiles

Removing and installing the outriggers (side stabilizers)

The outriggers are the stabilizers with wheels that are installed on the sides of the rack cabinet. After the
rack is in its final location and will not be moved more than 2 m (6 ft.), you can remove the outriggers.
DANGER:
Always relocate the rack cabinet with the outriggers installed. Keep the outriggers and install them if you
need to move the rack to another location in the future.
4
Installing the 7953-94X and 7965-94Y rack and features
45.97 mm
65.2 mm
65.2 mm
Approximate weight
179 kg (394 lb)
167 kg (367 lb)
142 kg (314 lb)
130 kg (287 lb)