2: General Description
2.5

Module control panel

Operator
menu buttons
2.5.1

Module mimic LED indicators

The module mimic LED colours change between GREEN, RED and OFF to
indicate the operational status of key UPS stages, and thereby serve to
show the active power path through the UPS.
• LINE 1 (rectifier) and LINE 2 (bypass) LEDs indicate the availability
of the input mains and bypass mains supplies respectively.
• INVERTER and BYPASS LEDs illuminate green to indicate which of
the two sources is providing the UPS output supply.
• BATTERY illuminates green when the battery is being charged and
flashes when the battery is discharging – e.g. when the inverter is
operating from battery power. The indication change to red if the
battery is faulty or fully discharged.
• Although it is not part of the module mimic, the ALARM LED, located
towards the lower-right of the control panel, provides a visual indication that an alarm condition has been detected.
When an alarm condition is present the LED is accompanied by an audible alarm.
14
LCD Power management display
Mimic LED indicators
Alarm LED/Reset
Figure 2.9 LCD Control panel
TS_615_01 PowerWAVE 8000DPA RI (S2) User Manual 8/6/20
Module ON/OFF
buttons (x2)
LINE 2
BYPASS
LINE 1
INVERTER
BATTERY
Figure 2.10 Module mimic diagram