2: General Description
This facility requires a purpose designed 'Multidrop' cable to be connected between each module's customer interface
board JD12.
Note that when the multidrop feature is used, the I/O facilities of customer interface board in the 'slave' cabinets are all
disabled, but the customer interface board fitted to the 'master' cabinet remains fully functional.
2.5.2

Parallel Interface Board

The parallel interface board facilitates the connection of the parallel control bus cables between the cabinets in a parallel
cabinet system. These cables are connected to a 'Parallel Adapter' board which is fitted to JD8.
2.6

Module control panel

A door-mounted module control panel is provided for each UPS module. The control panel is used to start and stop the
module, command a load transfer between inverter and bypass, and monitor the module's operating parameters. It is also
used to configure and interrogate the module during commissioning and troubleshooting.
Mimic LED Indicators
2.6.1

Module control panel buttons

The module control panel buttons allow you to:
• Start-up and shut down the UPS and transfer the load between inverter and bypass.
• Monitor and display the UPS operating voltages, currents, frequencies and other values on the LCD display.
• Reset/cancel an alarm.
Button function summary
BUTTON
FUNCTION
ON/OFF
Used to switch-on or switch-off the UPS by pressing both buttons simultaneously
Scroll upwards through a displayed menu
)
UP
Scroll downwards through a displayed menu
(
)
DOWN
ENTER
Selects a chosen menu item
RESET
Cancels an audible alarm. If the alarm condition is transient the ALARM LED will turn OFF, otherwise it will remain ON
ON/OFF Buttons
You can switch the UPS ON or OFF by simultaneously pressing both ON/OFF buttons (for less than 1s). The requirement
to press both buttons is to help prevent accidental operation.
16
Power Management Display (PMD)
Menu navigation &
Alarm & Reset
selection buttons
Figure 2.13 Module control panel