4.3
STIW400 Terminal Connections
PV1
PV2
NOTES:
1. The terminals accept 14-26AWG wire, and the screws shall be torqued to 0.4-0.5Nm (3.5 – 4.4
in-lb)
2. Any combination of sensor type inputs is allowed
3. Shielded cable is required for EMC conformity and is recommended for all remote sensor
installations. The shield shall be grounded at the transmitter end only.
4. When remote mounted probe sensors are used and the shield is grounded at the probe, the
shield shall not be connected at the transmitter end.
5. Duplex (redundant) sensors that are bonded to the probe are not permitted. All thermocouple/mV
and RTD/ohms inputs must be isolated from ground (the probe) and from each other.
6. Digital Input switches, DI, must be dry contact type, simple apparatus and properly segregated
from all other sources of power.
Revision 1
T/C or mV or DI or 2 Wire Resistance
+
-
+
-
TB1
3 Wire RTD or Resistance
PV1
TB1
3 Wire RTD or Resistance
PV1
TB1
Figure 4-1: STIW400 Terminal Connections
SmartLine Wireless Temperature and Universal I/O User's Manual
4. Sensor and Electrical Connections
4.3. STIW400 Terminal Connections
1
4
2
5
6
3
TB2
4
1
5
2
3
6
TB2
T/C or mV or DI or 2 Wire Resistance
4
1
5
2
3
6
TB2
+
PV3
-
+
PV4
-
PV3
+
PV3
-
+
PV4
-
31