Low Pressure Protection - Gree FGR20/BNa-M Service Manual

Duct type split air conditioner
Table of Contents

Advertisement

2.2 Low Pressure Protection

Compressor Low Pressure
Protection
Check if the refrigeration capacity
of the system is too low?
Check if the operational modes of the indoor
unit have been set correctly?
Check if the gas and liquid valves of the
outdoor unit are fully open?
Check if the panel of the outdoor unit has
been sealed?
Check if the ventilation of the heat
exchangers for the indoor and outdoor units
works properly?
Check if the fans for the indoor and outdoor
units are working?
Check if the swing blades of the indoor unit
are fully open?
Check if the capacity output of the outdoor
unit meets with the required capacity of the
indoor unit?
Check if the filter and heat exchange fins of
the outdoor unit are dirty or clogged?
the system pipe is clogged
Yes
No
No
Yes
No
Yes
No
Yes
No
Yes
Yes
No
No
Yes
No
Yes
Yes
No
Add refrigerant by referring to the refrigerant
volume specified on the nameplate and the
refrigerant volume calculated on Page?
refer to mode conflict
Fully open the valve
Cover the panel
Clear any obstacle
Check the fan motor
and the signal input
Check the swing motor and
the signal input
refer to capacity code
refer to maintenance
Duct Type Split Air Conditioner
Service Manual
53