Connection To Fresh Air Intake; Maintenance - Trane Jupiter JDAC Series Installation Operation & Maintenance

Close control units, chilled water units
Table of Contents

Advertisement

Connection to fresh air intake

The unit can be made ready for the intake of fresh air through an optional filter.
The optional module for the fresh air intake, containing the filter cartridge, must be applied on the left side of the unit
during the installation phase and correspond to the holes which introduce the air into the fan compartment.
During the installation phase connect a flexible circular duct, with a diameter equal to 80mm, to the nozzle which introduces
the air into the fan compartment and secure the duct to the nozzle with a fixing clamp.
the length of ducting between the air conditioner and the external air intake must be as short and straight as possible.
if the length of ducting is more than 6-8 metres, the use of an optional module for forced ventilation to be mounted in
line is recommended.
To replace the fresh air filter:
1- slide the protection cover of the fresh air module upwards.
2- remove the filter cartridge.
3- insert the new cartridge and reposition the protection cover.

Maintenance

Clean, using a blast of compressed air, or replace the fresh air intake filters periodically.
56