Operating Pressures - Trane EXWA Installation Manual

Water-to-water water-source heat pump
Table of Contents

Advertisement

Operating Pressures

Table OP-1: Cooling mode operating pressures
Unit Size
Entering
Load
(Degree F)
Suction
Pressure
EXWA 240
53.6
46-56
EXWA 240
86
61-71
Table OP-2: Heating mode operating pressures
Unit Size
Entering
Load
(Degree F)
Suction
Pressure
EXWA 240
75
46-56
EXWA 240
104
49-59
EXWA 240
122
49-59
22
Operating Pressures
Entering Source Temperature (Degree F)
50
86
Discharge
Suction
Discharge
Pressure
Pressure
Pressure
103-143
49-59
188-228
111-151
84-94
205-245
Entering Source Temperature (Degree F)
50
68
Discharge
Suction
Discharge
Pressure
Pressure
Pressure
160-200
65-75
170-210
245-285
68-78
254-294
310-350
68-78
320-360
104
Suction
Discharge
Pressure
Pressure
49-59
238-278
87-97
259-299
104
Suction
Discharge
Pressure
Pressure
86-96
183-223
94-107
268-308
95-105
333-373
WSHP-SVX02A-EN

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

GswdWpwd

Table of Contents