There is a short circuit on loop n
Fault
(Card n) wiring.
There is an open or short circuit
Fault
on the input line of an interface.
There is a mains supply failure at
Fault
an interface unit or a mimic panel.
The battery supply at an interface
Fault
unit or mimic panel has failed the
load test.
Identify the device where a
cable fault has occurred and
rectify the fault.
Locate and rectify the wiring
fault. Ensure the end-of-line
device is connected in the
circuit.
Check the mains fuse and
mains supply to the equipment.
Check the battery and replace
it if necessary.