Panasonic KW4M User Manual page 17

Eco-power meter
Table of Contents

Advertisement

Cutoff current setting mode
Mode defines load current that does not measured (Cutoff current).
Use to avoid miss-measurement by wiring or induction noise at no-load.
0.00kW is displayed for instantaneous electric power, 0.0A is displayed for current. Integrated
electrical energy is not measured.
・It can be set the range of 1.0% to 50.0%.
ex) When set to 10.0, current under 10.0%F.S is not measured.
Unit for pulse output setting mode (Power)
Mode defines unit used for pulse output.
・Select from 0.001/0.01/0.1/1/10/100kWh /Alarm.
When "ALARM" is set, alarm is output at the time when instantaneous electric power is over the
setting value.
When one of the "0.001/0.01/0.1/1/10/100"[kWh] is set, one pulse is output at the setting value.
Alarm value setting mode
Mode defines instantaneous electric power used for alarm output.
・It is set the range of 0.00 to 9999.99kW.
※This mode is only when " ALARM " is selected on unit for pulse output setting mode.
Electricity charge setting mode
Mode defines electricity charge ratio and conversion factor used as a standard per 1kWh.
The electricity charge ration of 5 kinds of currency (JPY,$,EUR,CNY,CHG) and CO
factor can be set.
・It can be set the range of 0.0 to 99.9 yen/1kWh. (Initial 10.0)
・It can be set the range of 0.000 to 9.999 dollars/1kWh. (Initial 0.093)
・It can be set the range of 0.000 to 9.999 euros/1kWh. (Initial 0.085)
・It can be set the range of 0.00 to 99.99 yuan/1kWh. (Initial 10.00)
・It can be set the range of 0.00 to 99.99 /1kWh. (Initial 10.00)
・CO
conversion factor can be set the range of 0.000 to 9.999 kg-CO
2
CT type setting mode
・ Press <kW/kWh> to change CT type.
・ CT type is selected from 50→100→250→400→5
Primary side current of CT setting mode
・ Enter primary side current of CT using
・ If measured CT is 100A/5A, set to 100.
・ If 5A is measured, set to 5.
It is only when " 5A " is selected on CT type setting mode.
C U T A
P L - P
A L - P
P Y / $ / E U R / C N Y / C H G / C O 2
Normal display
↓ <MODE>
MODE display
↓<kW/kWh>
↓ <SET>
<kW/kWh>,< A >, < V >.
↓ <SET>
2
/1kWh. (Initial 0.410)
2
Factory setting / Display
Factory setting / Display
conversion
11

Advertisement

Table of Contents
loading