Recommended Wire Size And Torque Requirements For Ups Input And Output Terminals - Toshiba 4200FA User Manual

Uninterruptible power system three-phase 15/ 25/ 30/ 33/ 50 kva ups
Hide thumbs Also See for 4200FA:
Table of Contents

Advertisement

4.3.1

Recommended Wire Size and Torque Requirements For UPS Input and Output Terminals

INPUT:
(H1) (H2) (H3)
AWG
208
220
240
380
400
415
480
600
All wire sizes are per the NEC. Maximum Wire Size for Input and Output is 1/0 AWG.
Neutral Conductors are rated @ 1.73 or 200% of phase conductors, per NEC. Maximum Wire Size for Neutral
is 250MCM.
Input/ Output (GND)
208-240VAC
380-480VAC
600VAC
Battery (+) / (-)
(+) (-)
Maximum Wire Size for Battery is 250MCM.
Minimum Wire Size and Torque requirements
UPS Optional Bypass Input Terminals TB4 50 kVA
(USE MINIMUM 75° C INSULATED COPPER WIRING)
Phase: (A) (B) (C)
Input: (H1) (H2) (H3)
208/120
220
240
380
400
415
480
600
Maximum Wire Size for Input is 1/0 AWG. Maximum Wire Size for Neutral is 250MCM.
TOSHIBA
Minimum Wire Size and Torque Requirements
UPS Input and Output Terminals 50 kVA
(USE MINIMUM 75° C INSULATED COPPER WIRING)
NEUTRAL
AWG
1/0
250MCM
1/0
4/0
1
N/A
4
1/0
4
1/0
4
1
6
2
6
N/A
50 kVA
AWG
Tightening Torque
6
6
8
50 kVA
AWG
Tightening Torque
250MCM
AWG
NEUTRAL AWG
1/0
250MCM
1/0
4/0
1
N/A
4
1/0
1/0
4
4
6
6
N/A
OUTPUT:
(L1)(L2)(L3)
AWG
208/120
1/0
220/127
1/0
240
1
380/220
4
400/230
4
415/240
4
480/277
6
600
6
200 in-lbs.
200 in-lbs.
200 in-lbs.
200 in-lbs.
50 kVA
Tightening Torque
200 in-lbs.
200 in-lbs.
200 in-lbs.
200 in-lbs.
200 in-lbs.
1
200 in-lbs.
2
200 in-lbs.
200 in-lbs.
25
NEUTRAL
Tightening
AWG
Torque
250MCM
200 in-lbs.
4/0
200 in-lbs.
N/A
200 in-lbs.
1/0
200 in-lbs.
1/0
200 in-lbs.
1
200 in-lbs.
2
200 in-lbs.
N/A
200 in-lbs.