13.7.2 Monitor Parameters

Parameter
Bit
0005
word
Output frequency monitor
0006
0
Run • stop status
1
Reserved
2
Forward • reverse status
3
Accel / decel #1 / #2 selection
status
4
Reserved
5
Reserved
6
Reserved
7
Jog mode status
8
Feedback enable status
9
Compulsory DC injection
braking mode
A
Fundamental parameter
switching
B
Coast stop command status
C
Emergency off command
D
Reserved
E
Reserved
F
Reserved
0007
word
Output current monitor
0008
word
Output voltage monitor (Note
1)
0009
word
IV terminal analog input value
000A
word
RX terminal analog input
value
000B
word
Frequency command monitor
000C
word
Input voltage monitor (Note 1)
000D
word
Input terminal status monitor
000E
low
Output terminal status
byte
monitor
high
Inverter Status 2
byte
000F
word
Inverter Status 1
0010
word
Present trip
0011
high
4th Past trip (most recent)
byte
low
3rd past trip
byte
Function
Bank
0
0
0
0
0
0
0
0
0
0
0
0
0
65
Mask
Adjustment Range
FFFF
0.00 ~ 400.00Hz
0: Stopped
1: Running
0: Reverse
1: Forward
0: Accel / decel #1
1: Accel / decel #2
0: Normal (accel /
decel mode)
1: Jog mode
0: Feedback invalid
1: Feedback valid
0: DC injection braking
inactive
1: DC injection braking
active
0: V/F #1
1: V/F #2
0: Normal
1: Coast to stop
0: Normal
1: Emergency off
00FF
0 ~ 255%
FFFF
0 ~ 232%
FFFF
0000 ~ FFFF (0% ~
100%)
0000 ~ 7FFF (-100% ~
FFFF
0%), 7FFF ~ FFFF
(0% ~ 100%)
0000 ∼ 9C40
FFFF
(0.00 ∼ 400.00 Hz)
FFFF
0 ~ 255%
FFFF
Refer to Table 5 (page
67)
00FF
Refer to Table 6 (page
67)
FF00
FFFF
Refer to Table 7 (page
68)
00FF
7F00
007F
Refer to section
13.7.16 for fault codes
Multiplier
0.01
1
0.1
1
1
0.01
0.1