Trane BACnet BCI-R Integration Manual page 33

Communication interface for reliatel controllers
Table of Contents

Advertisement

Table 11. All Object Types Sorted by Object Name (
Object Identifier
Object Name
Analog Input, 8
Exhaust Fan Speed Command
Multi-State Input, 38
Exhaust Fan Status
Analog Output, 33
Exhaust or Return Fan Configuration
Analog Input, 90
Exhaust or Return Fan Type
Analog Input, 6
Filter Runtime Hours
Analog Value, 1
Filter Runtime Hours Setpoint
Binary Output, 13
Filter Timer Reset
Analog Output, 20
Heat Capacity Enable Setpoint BAS
Multi-State Output, 8
Heat Cool Mode Request BAS
Binary Output, 5
Heat Lockout Command
Multi-State Input, 29
Heat Output 1
Multi-State Input, 30
Heat Output 2
Multi-State Input, 31
Heat Output 3
Multi-State Input, 32
Heat Output 4
Analog Input, 2
Heat Primary Capacity Status
Analog Input, 3
Heat Secondary Capacity Status
Multi-State Input, 23
Heating Setpoint Source
Binary Output, 19
Lead-Lag Enable Command
Analog Input, 25
Mixed Air Temperature
Binary Output, 20
Morning Warmup Enable Command
Analog Output, 4
Morning Warmup Setpoint BAS
Analog Input, 54
Morning Warmup Temperature Setpoint Active
Multi-State Output, 7
Occupancy Request
Multi-State Input, 20
Occupancy Status
Analog Output, 29
Occupied Offset
Analog Input, 11
Outdoor Air Damper Position Status
Analog Input, 34
Outdoor Air Flow Active
Analog Input, 20
Outdoor Air Humidity Active
Analog Output, 15
Outdoor Air Humidity BAS
Analog Input, 57
Outdoor Air Minimum Flow Setpoint Active
Analog Output, 16
Outdoor Air Minimum Flow Setpoint BAS
Analog Input, 18
Outdoor Air Temperature Active
Analog Output, 14
Outdoor Air Temperature BAS
Multi-State Input, 43
Outdoor Damper Status
Analog Output, 34
Power Exhaust Enable Setpoint BAS
Analog Input, 82
Preheat Type
Multi-State Input, 35
Primary Filter Status
Analog Input, 5
Reheat Capacity Status
Analog Input, 83
Reheat Type
Binary Output, 14
Reset Diagnostic
Analog Input, 26
Return Air Temperature
Analog Input, 97
RTAM Major Version
Analog Input, 98
RTAM Minor Version
Analog Input, 105
RTCM Major Version
Analog Input, 106
RTCM Minor Version
Analog Input, 101
RTDM Major Version
BAS-SVP09B-EN
Object Data Points and Diagnostic Data Points
Refer to previous tables for detailed descriptions of objects
Description
Indicates the unit commanded exhaust fan speed.
Indicates the commanded state of the exhaust fan.
Sets the equipment exhaust or return fan type.
Describes the exhaust or return fan type installed in the unit.
Indicates the number of hours air has flowed through the filter.
The setpoint value used by the filter run hours calculation.
Command the unit to reset the accumulated filter run hours.
BAS supplied heating demand limit capacity setpoint value.
Command the unit to a specific application mode.
Command the unit to prevent heating operation.
Indicates the commanded state of heating output 1.
Indicates the commanded state of heating output 2.
Indicates the commanded state of heating output 3.
Indicates the commanded state of heating output 4.
Indicates the unit primary heating capacity being utilized.
Indicates the unit secondary heating capacity being utilized.
Indicates the source of the space heating setpoint.
Command the unit compressor startup order
The mixed air temperature value from a unit-mounted sensor.
Command the unit morning warmup operation
BAS supplied temperature setpoint used in morning warmup mode.
The air temperature setpoint used during morning warmup mode.
Command the unit into an occupancy mode.
Indicates the current occupancy mode of the unit.
Offset used to calculate setpoints in occupied mode.
Indicates the unit outdoor air damper position.
Outdoor airflow utilitzed by the unit.
The outdoor air humidity value used for unit control.
BAS supplied outdoor air humidity sensor value.
The minimum outdoor airflow setpoint being utilized by the unit.
BAS supplied minimum outdoor airflow setpoint.
The outdoor air temperature currently used for unit control.
BAS supplied outdoor air temperature sensor value.
Indicates the operating state of the outdoor damper.
BAS supplied power exhaust enabled setpoint value.
Describes the heating type installed in the unit.
Indicates the primary filter media state.
Indicates the unit reheat heating capacity being utilized.
Describes the reheat type installed in the unit.
Command the unit to reset and clear diagnostics.
The return air temperature value from a unit-mounted sensor.
Major software version number of the RTAM module
Minor software version number of the RTAM module
Major software version number of the RTCM module
Minor software version number of the RTCM module
Major software version number of the RTDM module
) (continued)
33