Object Data Points and Diagnostic Data Points

For quick reference, the following tables are listed two different ways. Tables 3 through 9 are listed
by input/output type and sorted by object identifier. These tables provide the user with the units
type for each object type.
a complete list of object names, types, values/ranges, and descriptions. Not all points are available
to the user. The available data points are defined during self-configuration and are dependent on
the type of equipment.
Table 3.
Analog Output
Object Identifier Object Name
Analog Output, 1
Economizer Minimum Position Setpoint BAS
Analog Output, 2
Space Temperature Setpoint BAS
Analog Output, 4
Morning Warmup Setpoint BAS
Daytime Warmup Terminate Temperature
Analog Output, 5
Setpoint BAS
Analog Output, 6
Discharge Air Cooling Setpoint BAS
Analog Output, 7
Discharge Air Heating Setpoint BAS
Analog Output, 8
Duct Static Pressure Setpoint BAS
Analog Output, 9
Space Static Pressure Setpoint BAS
Analog Output, 10
Space Static Pressure BAS
Analog Output, 11
Space Temperature BAS
Analog Output, 14
Outdoor Air Temperature BAS
Analog Output, 15
Outdoor Air Humidity BAS
Analog Output, 16
Outdoor Air Minimum Flow Setpoint BAS
Analog Output, 18
Space CO
2
Analog Output, 19
Cool Capacity Enable Setpoint BAS
Analog Output, 20
Heat Capacity Enable Setpoint BAS
Analog Output, 21
Space Dehumidification Setpoint BAS
Analog Output, 23
Discharge Air Reheat Setpoint BAS
Analog Output, 25
Space Humidity BAS
Analog Output, 29
Occupied Offset
Analog Output, 30
Standby Offset
Analog Output, 31
Unoccupied Cooling Setpoint
Analog Output, 32
Unoccupied Heating Setpoint
24
Table 11, p. 32
Description
BAS supplied economizer
position minimum setpoint value
Base value to calculate setpoints
in occupied and standby modes.
BAS supplied temperature
setpoint used in morning
warmup mode.
BAS supplied daytime warmup
terminate temperature setpoint.
BAS supplied discharge air
temperature cooling setpoint
value.
BAS supplied discharge air
temperature heating setpoint
value.
BAS supplied duct static air
pressure setpoint value.
BAS supplied space static air
pressure setpoint value.
BAS supplied space static air
pressure sensor value.
BAS supplied space air
temperature sensor value.
BAS supplied outdoor air
temperature sensor value.
BAS supplied outdoor air
humidity sensor value.
BAS supplied minimum outdoor
airflow setpoint.
BAS supplied space CO
Concentration BAS
value.
BAS supplied cooling demand
limit capacity setpoint value.
BAS supplied heating demand
limit capacity setpoint value.
BAS supplied space
dehumidification setpoint value.
BAS supplied discharge air
reheat setpoint value.
BAS supplied space humidity
sensor value.
Offset used to calculate setpoints
in occupied mode.
Offset value used to calculate
setpoints in standby mode.
Cooling temperature setpoint
used for control in unoccupied
mode.
Heating temperature setpoint
used for control in unoccupied
mode.
and
Table 13, p. 35
are sorted by object name and provide
Units of Measure
IP/SI
Percent (98)
Fahrenheit (64)
Celcius (62)
Fahrenheit (64)
Celcius (62)
Fahrenheit (64)
Celcius (62)
Fahrenheit (64)
Celcius (62)
Fahrenheit (64)
Celcius (62)
0.0 inH2O = 0 Pa (53)
2.5 inH2O = 622 Pa
-0.2 inH2O = -50 Pa (53)
0.3 inH2O = 74 Pa
-0.67 inH2O = -167 Pa (53)
0.67 inH2O = 167 Pa
Fahrenheit (64)
Celcius (62)
Fahrenheit (64)
Celcius (62)
Percent (98)
0 CFM = 0 l/s (litres/second)
60000 CFM = 28317 l/s (87)
sensor
Part-per-million (96)
2
mg/kg
Percent (98)
Percent (98)
Percent (98)
Fahrenheit (64)
Celcius (62)
Percent (98)
Fahrenheit (64)
Celcius (62)
Fahrenheit (64)
Celcius
Fahrenheit (64)
Celcius (62)
Fahrenheit (64)
Celcius (62)
Refresh
Rate
Valid Range
(Sec.)
0 to 100
NA
50.0 to 90.0
NA
10.0 to 32.2
50.0 to 90.0
NA
10.0 to 32.2
50.0 to 87.0
NA
10.0 to 30.6
40.0 to 90.0
NA
4.4 to 32.2
40.0 to 180.0
NA
4.4 to 82.2
0.0 to 2.5
NA
0.3 to -0.2
NA
-0.67 to 0.67
900
-39.5 to 200.0
900
-39.7 to 93.3
-39.5 to 200.0
900
-39.7 to 93.3
10.0 to 90.0
900
0 to 60,000
NA
0.0 to 2000
900
0 to 100
NA
0 to 100
NA
40 to 65
NA
65.0 to 80.0
NA
18.3 to 26.7
10 to 90
900
1.0 to 5.0
NA
-17.2 to -15.0
1.0 to 5.0
NA
-17.2 to -15.0
52.0 to 88.0
NA
111.1 to 31.1
50.0 to 90.0
NA
10.0 to 32.2