Priorities in the block when setting commands
1. Restart or higher-level error (QCSF)
2. Local operation or Simocode Overload (OVL) function
3. Interlocking with LOCK
4. Interlocking with LOCK_ON and LOCK_OPT or VL_OPEN, VL_CLOSE, VL_HOLD
5. AUTO with AUTO_M
6. AUTO
7. MANUAL LINKED
8. MANUAL OPERATOR
The commands are set in positions 3-8. A command is reset when the associated check-
back signal is present, or an associated equivalent signal, or a higher-level error or general
fault occur in SIMOCODE DP.
Note
For control functions REV, POL, and POS, the appropriate opposite direction or speed is
switched on only after the lock time configured in SIMOCODE-DP has elapsed (this is
indicated on output QLTA and the Lock time active display in the Standard view.
SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.0 SP2
Programming and Operating Manual, 09/2019, A5E48307694002A/RS-AA/001
SIMO_CHN Function