I/O Parameter
Meaning
CUR_AL
LL Alarm Limit in %Is
CUR_MIN
Discrimination threshold for monitoring
Cur in %Is
CUR_QC
Quality Code for Cur
CUR_WH
H Alarm Limit (Warning) in %Is
CUR_WL
L Alarm Limit (Warning) in %Is
EM_START
SIMOCODE DP 0.4: 1=emergency start
EN_SD_CS
1= enable operator updating of record
131/130
EXTMSGTXT
Text of external Message
EXTMSGVAL
external Message Value
HYS
Hysteresis of current, (Hys>=0)
I1_0
SIMOCODE: DP Receive Bit 1.0
I1_1
SIMOCODE: DP Receive Bit 1.1
I1_2
SIMOCODE: DP Receive Bit 1.2
I1_3
SIMOCODE: DP Receive Bit 1.3
I1_4
SIMOCODE: DP Receive Bit 1.4
I1_5
SIMOCODE: DP Receive Bit 1.5
I1_6
SIMOCODE: DP Receive Bit 1.6
I1_7
SIMOCODE: DP Receive Bit 1.7
I23
SIMOCODE: DP Receive Bit 2.0 - 3.7
INBT2_01
process value DP 0.0-1.7 basic type 2
INBT2_23
process value motor current basic type 2
L_CS_UPD
linkable input: 0->1: update record 130
L_OFF
MANUAL LINKED: 1=switch off/stop
L_ON1
MANUAL LINKED: 0->1=switch
slow/reverse/close
L_ON2
MANUAL LINKED: 0->1=switch
on/fast/forward/open
L_RESET
Linkable Input RESET
L_SD_UPD
linkable input: 0->1: update record 131
L_SIMORESET
Linkable Input SIMORESET
LADDR
Logical address of module
LIOP_SEL
Operating mode: 1=linking; 0=operator
active
LOCK
1=Lock/Lock to SS_POS
LOCK_ON
1=Lock ON
LOCK_OPT
LOCK_ON=1: 0=ON2, 1=ON1
LOCKED
1=SIMOCODE - LOCKED
LOCOP_EN
ENABLE: 1=operator may input LOCAL
M_SUP_C
1=Suppress current limit messages
M_SUP_EXT
1=Suppress external Message
SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.0 SP2
Programming and Operating Manual, 09/2019, A5E48307694002A/RS-AA/001
Data Type
Default setting Type
REAL
70
REAL
20
BYTE
16#80
REAL
115
REAL
80
BOOL
FALSE
BOOL
TRUE
STRING[1 6] ''
DWORD
16#0
REAL
3
BOOL
FALSE
BOOL
FALSE
BOOL
FALSE
BOOL
FALSE
BOOL
FALSE
BOOL
FALSE
BOOL
FALSE
BOOL
FALSE
WORD
16#0
WORD
16#0
WORD
16#0
BOOL
FALSE
BOOL
FALSE
BOOL
FALSE
BOOL
FALSE
BOOL
FALSE
BOOL
FALSE
BOOL
FALSE
INT
0
BOOL
FALSE
BOOL
FALSE
BOOL
FALSE
BOOL
FALSE
BOOL
FALSE
BOOL
TRUE
BOOL
FALSE
BOOL
FALSE
SIMO_CHN Function
3.2 Inputs / Outputs
OCM
Permissible
Values
I
+
I
>=20
O
+
I
+
I
+
I
+
I
I
I
I
+
>=0
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
+
I
+
I
+
O
+
I
IO
+
I
+
23