Cabinet Design and EMC

12.5 Electromagnetic Compatibility

Commissioning
Caution
The system must only be vented once it has been disconnected from the power supply.
• When the equipment is filled for the first time, the heat sinks must be vented.
• Remove the safety seal screws in front of the vent valve.
• Vent the system.
• Close the vent valve.
• Replace the safety seal screws.
• Ensure that they are tight.
• The operating pressure must be set in accordance with the flow conditions of the cooling
• The required cooling quantity per time unit must be set.
12.5
Electromagnetic Compatibility
12.5
12.5.1

General

EMC requirements can be found in EN 60439-1 and recommendations in EN 60204-1. For
installation of components in cabinets, the following conditions must be ensured to comply
with the EMC Directive:
• Operation in TN systems with SINAMICS line filters
• Observance of information about cable shielding and equipotential bonding
• Use of recommended Siemens power and signal cables.
• Only Siemens cables may be used for DRIVE-CLiQ connections.
For MOTION-CONNECT cables please refer to Catalog D21.1 or D21.2.
12-20
water network in the infeed and return line.
Caution
No couplings or self-made cables may be used for the DRIVE-CLiQ connections.
Equipment Manual Booksize Cold-Plate Power Sections
Manual, (GH4), Edition 06.2005, 6SL3097-2AJ00-0BP2