1 x FBI4500-0100
Product information

General safety regulations

Attention! Mounting, installation, commissioning and repair of electronic devices have
!
to be carried out only by qualified electricians. The latest accident prevention regulati-
ons must be observed.
For working on systems with main connection of 230 V alternating voltage, the safety re-
quirements according to DIN VDE 0100 must be observed.
When installing TCS:BUS
systems according to VDE 0800 must be observed. Inter alia:
 separated conduit of heavy current and low current lines,
 minimum distance of 10 cm in case of a common conduit,
 use of separators between heavy and low current lines within shared cable ducts,
 use of standard communication lines, e.g. J-Y (St) Y with a diamter of 0.8 mm,
 exisiting lines (modernisation) with deviating cross-sections can be used in compliance
with the loop resistance.
Installation – protective measures
With suitable measures to protect against lightning, it has to be ensured that a voltage
!
of 32 V DC is not exceeded at the connections a, b, E, P, M, V1, V2, V, ┴ , +, −.
TCS TürControlSysteme AG  TCS Hotline: +49 (0) 41 94 / 98 81 188
FAX: +49 (0) 41 94 / 98 81 29  Mail: hotline@tcsag.de
3

Scope of delivery

Safety instructions

®
systems, the general safety regulations for telecommunication
Subject to technical changes.