Troubleshooting - Buffer Module Cpm-1-70, Buffer Cylinder Spu-1-200 - Wolf DHW Series Installation Instructions Manual

Hide thumbs Also See for DHW Series:
Table of Contents

Advertisement

Fault
Cause
Leaks
Pipe connections leaking
Heat-up time too long
Heating water temperature too low; measure at
cylinder flow, not at heat generator
Heating circuit not vented
Cylinder sensor not in sensor well
No / insufficient
Controller for cylinder return temperature control
unloading of cylinder
poorly adjusted
on heating water side
Diverter valve faulty / incorrectly connected
Flow rate on heating side too low
42
36. Troubleshooting – buffer module
CPM-1-70, buffer cylinder SPU-1-200
Remedy
Re-seal the connections
Increase temperature (adjust controller)
Vent several times (see manual air-vent valve)
Check position of cylinder sensor
Change parameters (in particular start
temperature differential)
Re-establish function
Vent heating circuit
Remove blockages
Increase pump rate
3064300_201703