Indicators - Siemens FC1008-A Technical Specification

Fire control unit
Table of Contents

Advertisement

Operation and indicator elements, mode of operation (PMI)
6.1.2

Indicators

LED
Labeling
1
System ON
2
Fault
3 and 4
ALARM
5
Remote transmis-
sion
6
Operating access
7
System part
disabled
8
Detector test
9
Mode manned
10
Earth fault
11
Power fault
12
System fault
13
Alarm horn
disabled / fault
14
Controls disabled
15
RT-Fault
disabled / fault
17 (2/4)
RT-Alarm dis-
23 (8/12)
abled
22
Building Technologies
Fire Safety & Security Products
LED
1
2
3
4
5
6
1
2
3
LED
State active
on
if system is in operation (micro computer working)
fast
if any system part is on Fault
buzzer with pulsating sound
on
if system is on Alarm
either
slow
flashing alternating while V1/V2 are running (programmable step 4)
or
fast
flashing synchronous on unacknowledged (programmable step 4)
on
if contact RT-Alarm is active
if programmed also if contact RT-Fault is active
on
if operating access is provided
timeout 3 min. after last key operation
on
if any system part is disabled or a zone is in mode detector test
slow
if system is in operating mode manned
on
if system is in operating mode manned
without function if all zones are set to direct or internal,
see chapter Processing diagram
fast
if any system part has short circuit to earth
fast
if battery is disconnected or low
slow
if mains supply voltage is missing or to low (after delay has expired)
on
if micro-computer has failed (system not working)
on
if horn control lines are disabled
fast
if horn control line has a break or short
slow
if horn control lines are in mode walk-test
on
if zone control outputs are disabled
fast
if control line programmed as fire control has a break or short (step 5, option 12, 13)
on
if contact RT-Fault is disabled
fast
if programmable control input with option 1 is active (Fault remote transmission device)
control input Fault RT is active
if control line programmed as fire control has a break or short (step 5, option 14)
on
if contact RT-ALARM is disabled
fast
if control line programmed as RT-Alarm has a break or short (step 5, option 11)
LED
7
8
9
10
11
12
13
14
15
4
17
A6V10265083_a_en_--
03.2010