System description
3.3

Specified standards and options

EN54-2
Basic functions
Options and associated requirements
Output to fire alarm device EN54-1 / C
7.8
( Fire alarm devices )
7.9.1
Output to fire alarm routing equipment EN54-1 / E
7.9.2
Alarm confirmation input from fire alarm routing equipment
7.10.1
Outputs to fire protection equipment EN54-1 / G
Outputs to fire protection equipment
7.10.2
Output type B EN54-1 / G
7.10.3
Outputs to fire protection equipment
7.10.4
Fault monitoring of fire protection equipment
7.11.1
Delays to outputs V1/V2 timer for alarm organization
7.11.2
Switch on /off delays to outputs, V1/V2 timer for alarm organization
Dependencies on more than one alarm signal
7.12.1
Type A dependency from the same detector, or another in the same
line
Dependencies on more than one alarm signal
7.12.2
Type B dependency cross zoning
Dependencies on more than one alarm signal
7.12.3
Type C dependency (option with requirement)
7.13
Alarm counter (option with requirement)
8.3
Fault signals from points (option with requirements)
8.4
Total loss of the power supply (option with requirements)
8.9
Output to fault warning routing equipment according EN54-1 / J
10
Test condition (option with requirements)
Standardized input/output interface (option with requirements – see
11
also Annex G)
Remarks:
* the panel provides in the standard 2 monitored control lines and with the FCA1003 control card 4 additional moni-
tored outputs. In step 5 we provide for output the options.
3.4

System overview

DC1192
EX-area
SB3
24 V
10
Building Technologies
Fire Safety & Security Products
AC power input
115/230 VAC
Related FC10 configuration /
connection
Sounder line 1
Step 5 option 1
Step 4 option 7
Sounder line 3
Step 5 option 11
n/a
Sounder line 1
Step 5 option 13
Step 1 & 2 (timer V1 & V2)
Key 8 (Manned / unmanned)
Step 6 / option 2
Step 11 option 4
n/a
FCA1002 display unit
Zone Led
and LED 9
n/a
Sounder line 6
Step 5 option 14
Push Key zone x
n/a
Fire controls
max. 6 relays
A6V10265083_a_en_--
Fulfilled
x
Fulfilled
x*
x*
-
x*
-
-
-
x
x
x
x
-
x
x
-
x
x
-
03.2010