Siemens SIMATIC Manual page 82

Pid temperature control
Hide thumbs Also See for SIMATIC:
Table of Contents

Advertisement

Appendix
Addr Parameter
Decl.
24.2
QLMN_LLM OUTPUT BOOL
24.3
QC_ACT
OUTPUT BOOL
26.0
CYCLE
INPUT/
OUTPUT
30.0
CYCLE_P
INPUT/
OUTPUT
34.0
SP_INT
INPUT/
OUTPUT
38.0
MAN
INPUT/
OUTPUT
42.0
COM_RST
INPUT/
OUTPUT
42.1
MAN_ON
INPUT/
OUTPUT
A-4
Data
Range of
Initial
Type
values
Value
FALSE
TRUE
≥ 0.001 s
REAL
0.1 s
≥ 0.001 s
REAL
0.02 s
REAL
Depen-
0.0
dent on
the
sensors
used
REAL
0.0
BOOL
FALSE
BOOL
TRUE
Description
LOW LIMIT OF MANIPULATED
VARIABLE REACHED
The value of the manipulated variable
is always limited to an upper and
lower limit. The QLMN_LLM output
indicates when the lower limit is
exceeded.
NEXT CYCLE, THE CONTINUOUS
CONTROLLER IS WORKING
This parameter indicates whether or
not the continuous controller stage
will be executed at the next block call
(relevant only when SELECT has the
value 0 or 1).
SAMPLE TIME OF CONTINUOUS
CONTROLLER [s]
This sets the sampling time for the
PID algorithm. The tuner calculates
the sampling time in Phase 1 and
enters this in CYCLE.
SAMPLE TIME OF PULSE
GENERATOR [s]
At this input, you enter the sampling
time for the pulse generator stage.
FB 58 "TCONT_CP" calculates the
sampling time in Phase 1 and enters
it in CYCLE_P.
INTERNAL SETPOINT
The "Internal Setpoint" input is used
to specify a setpoint.
MANUAL VALUE
The "Manual Value" input is used to
specify a manual value. In automatic
mode, it is corrected to the
manipulated variable.
COMPLETE RESTART
The block has an initialization routine
that is processed when the
COM_RST input is set.
MANUAL OPERATION ON
If the "Manual Operation On" input is
set, the control loop is interrupted.
The MAN manual value is set as the
value of the manipulated variable.
PID Temperature Control
A5E00125039-02