Siemens SIMATIC Manual page 49

Pid temperature control
Hide thumbs Also See for SIMATIC:
Table of Contents

Advertisement

Example of Weakening the Control Response with PFAC_SP
Process parameters:
GAIN = 6
T1
T2
Controller parameters:
GAIN = 1.45
TI
Process value
The figure below shows three attempts each with a setpoint step change from
0 to 60:
Attempt
PFAC_SP
Left 8:18
1.0
Middle 8:19
0.8
Right 8:20
0.0
PID Temperature Control
A5E00125039-02
= 50 s
= 5 s;
= 19.6 s
Comment
No P-action in the feedback;
undamped control response
20% P-action in the feedback;
optimum control response
Complete P-action in the feedback;
too strongly damped, long transient response
Controller Tuning in FB 58 "TCONT_CP"
Setpoint
Process value
Manip. variable
Overshoot
32 %
2 %
-
3-17