9: Specification
INPUT CHARACTERISTICS (Continued)
Rated short time withstand current
AC Power distribution system
Required input connection
BATTERY CHARACTERISTICS
Battery type
Variable number of 12V battery blocks
Variable number of 1.2V NiCd cells
Max. battery charger current
Max. battery charger power
Battery float voltage (VRLA / NiCd)
End of discharge voltage (VRLA / NiCd)
Temperature controlled charger
Ripple current (rms)
Battery test
OUTPUT CHARACTERISTICS
Output rated power
(@min 42 battery blocks)
Load power factor rated
Output current (In)
(PF=1.0) (@min 42 battery blocks)
Output rated voltage
Output waveform
Output voltage stability (normal/battery mode)
Total harmonic distortion with 100% load
operating in normal mode
Total harmonic distortion with 100% load
operating in battery mode
Voltage transient and recovery time with
100% step load
Output frequency
Output frequency tolerance
Frequency slew rate
Max synch phase error
Permissible unbalanced load
Overload capability on inverter
Fault clearing capability (100ms)
Bypass short circuit capability
52
60
10kA for 1.5 seconds
TN-S, TN-C, TN-C-S, TT
3 phases an neutral required
60
Maintenance-free VRLA, vented lead-acid, NiCd
No.
42-48
Autonomies >60 min are only available for loads < 90%.
For loads between 90-100%, the maximum allowed autonomy is 60 mins.
For autonomy's less than 20 mins UPS supports 42-50 x12 V blocks
No.
420-480
Autonomies >60 min are only available for loads < 90%.
For loads between 90-100%, the maximum allowed autonomy is 60 mins.
For autonomy's less than 20 mins UPS supports 420-500 x1.2V cells
A
37
kW
18
VDC
2.25 / 1.40
VDC
1.65 / 1.05
Yes (temperature sensor optional)
%
2% of the battery capacity
Automatic and periodic (adjustable)
60
kVA/
60/60
kW
1.0
A
87
V
3x 380/220 or 3x 400/230 or 3x 415/250
Sinewave with 0deg. phase imbalance @100% unbalanced load
%
± 1.5 / ± 1.5
%
< 2 with linear load
%
< 2 with linear load
%/
< 4% (linear load)
sec
Hz
50 or 60
%
±0.1 free-running, quartz oscillator
±2 or ±4 (selectable) with mains synchronised
Hz/s
1.0
°
< 2° (referred to a 360° cycle)
%
100% (all 3 phases independently regulated)
% /
150% load for 30 seconds
min
125% load for 5 minutes
110% load for 20 minutes
A
2x In for normal mode and battery mode
A
10x rated In for 10ms
TS_610_01 PowerWAVE 6000 S3 (60-120kVA) User Manual 21/10/19
80
100
80
100
49
61
24
30
80
100
80/80
100/100
116
145
120
120
61
30
120
120/120
174