Various remote monitoring and control facilities can be connected to the communications interface board located in the
front, lower right-hand corner of the UPS module. The external cables enter the cabinet through the cabinet floor in the
same manner as the power cables.
Although all connected features will be checked by the commissioning engineer when the UPS system is commissioned,
they can be connected by the customer installation team at this point provided no external power is applied to the circuits
until they have been properly commissioned. Details of the interface facilities and other options are provided in Chapter 8.
Key Point: In a parallel system UPS cabinet a 'parallel adapter' board is fitted to the [JD1 Parallel Bus]
connector which is in turn connected to the parallel control bus cables that pass between every module.
Similarly an inter-module cable is connected to the Multidrop RJ45 connectors.
These cables must be installed and configured by the commissioning engineer; however, depending on the
position of the cabinets, it may be necessary for the customer to provide any necessary cable containment.
Contact Kohler Uninterruptible Power Ltd for further installation advice if required.
TS_610_01 PowerWAVE 6000 S3 (60-120kVA) User Manual 21/10/19