Connecting
7.7 PROFINET
Table 7- 17
Cable
IE FC Cable GP 2 (Type A)
IE FC Flexible Cable GP 2
(Type A)
IE FC Trailing Cable GP 2x2
(Type C)
IE FC Trailing Cable 2x2
(Type C)
IE FC Marine Cable 2x2
7.7.3

Preparing the twisted pair cables

Function
The IE FC RJ45 Plugs are used to install uncrossed 100 Mbit/s Ethernet connections up to
100 m without the use of patches. Crossed cables can also be installed by swapping the
transmit and receive pair in a plug.
Prerequisite
When you set up your PROFINET system, you can cut the AWG 22 twisted pair cable on-
site to the required length, strip it with the
Ethernet), and fit the
technique.
Proceed as follows
Contacting of the FC cable versions is simple and reliable with the 4 integrated insulation
displacement contacts.
● When the plug case is open, color markings on the contact cover make it easier to
● The stripped end of the cable is inserted in the raised insulation displacement terminals
58
Cable types for PROFINET
Industrial Ethernet FastConnect RJ-45 Plugs
connect the cores to the insulation piercing connecting devices. The user can check that
contact has been made correctly through the transparent plastic material of the contact
cover.
and the terminals are then pressed down to ensure reliable contacting of the conductors.
Designation
4-wire, shielded TP installation cable for IE FC
RJ45
4-wire, shielded flexible TP installation cable
for IE FC RJ45
4-wire TP installation cable for ground cable
use
4-wire shielded TP installation cable for
connection to FC OUTLET RJ45, for ground
cable use
4-wire shielded marine-certified TP installation
cable for connection to FC OUTLET RJ45
Fast Connect Stripping Tool
Order number
6XV1 840-2AH10
6XV1 870-2B
6XV1 870-2D
6XV1 840-3AH10
6XV1 840-4AH10
(for Industrial
using the cut-and-clamp
NCU 7x0.3 PN
Manual, 09/2011, 6FC5397-1EP40-0BA0