GENERAL INSTALLATION INFORMATION

GAS SUPPLY

Gas pipe sizing must consider the gas input to this appliance as well as all other gas appliances
in the premises. The gas meter and regulator must be specified for the total gas rate.
WARNING
A suitable sizing chart such as the one in AS/NZS 5601 should be used.
Confirm correct gas type (see labels located on top or rear panels). Refer to local gas authority
for confirmation of gas type if you are in doubt.
IMPORTANT

Installation of consumer piping

The gas supply (consumer piping), termination is inside the heater and enters
through the rear of the appliance.
A ½" BSP flared nut (a) and a ½" BSP Male Flare x ½" Barrel Union - Elbow
(b) are provided for connection to the consumer piping (c). They are shipped
inside the engine attached to on the gas inlet connection of the heater.
Refer to the table below and the dimensional drawings on this page and on
page 16 for appliance gas inlet location and other relevant dimensions.
1.
Mark off the location for the vertical centre line (1) of the heater enclosure.
2.
To the right of the vertical centre line (1), mark off both the vertical (2) and
horizontal (3) location for the gas supply penetration (consumer piping).
For measurements refer to the Gas Supply Dimension Table below.
The length of the gas supply (consumer piping) termination
(4) is measured from the front of the enclosure including the
thickness of any cladding material.
CAUTION

Gas Supply Dimension Table

2
280mm to right of appliance centre-line (1)
3
43mm from base of enclosure
4
Consumer piping to be terminated 79mm from the front of enclosure

Purging Gas Supply

Foreign materials and debris such as swarf, filings, etc. MUST be purged / removed from the gas supply, failure
to do so may cause damage to the gas control valve causing it to malfunction.

Leak Testing the Connection

Plug the end of the consumer piping gas and leak test all joints.
Use a soapy solution to test all gas connections. If a leak is present bubbles will form at the leak
point. When finished remove any residue with a rag. Prevent any soapy solution from coming in
contact with electrical components.
CAUTION

ELECTRICAL SUPPLY

If a power point is used it MUST be 230 V, rated at 10A and MUST be earthed.
This power point MUST NOT be located above the heater. The heater engine
is fitted with a 1.5 metre power cord and three pin plug which can exit the
appliance from either the lower left or right hand side of the heater as required.

Direct Wired Installations

Alternatively the appliance can be direct wired to conceal the power supply.
A qualified electrician will need to be consulted where a direct wired installation is required. Any
such installation must comply with the requirements of AS/NZS 5601, AS/NZS 3000 and any other
relevant local regulations.
IMPORTANT
Rinnai
16
a
c
b
Gas supply location
1
2
4
Gas supply pressure to be 1.13 to 2.75 kPa
Power Cord
Rubber Grommet
RIBF25 OIM
3