Programming "Default" Values - York eco2 YCAS0425EB Installation Operation & Maintenance

Air-cooled screw liquid chillers
Table of Contents

Advertisement

If manual control is desired, press the á or â key. One
of the following messages will be displayed:
L E A D / L A G
C O N T R O L
M A N U A L
S Y S
L E A D / L A G
C O N T R O L
M A N U A L
S Y S
System 1, 2, 3 or 4 can be selected as the lead by press-
ing the á or â key. The ENTER key must be pressed
to save the selection in memory.
Automatic/Manual Power Failure Restart
P O W E R
F A I L
A U T O M A T I C
The chiller may be selected for "Automatic" or
"Manual" restart after a power failure. In most instances,
"Automatic Restart" is preferred to allow the chiller to
automatically restart when power is reapplied after a
power failure. When "Manual" is selected, the chiller
will not operate after re-application of power until the
ON / OFF Rocker Switch on the keypad is cycled OFF
and then ON.
In most applications, it is undesirable
to use Manual Reset on power failure
since chillers normally are required to
auto-restart after a power failure.
8.3

PROGRAMMING "DEFAULT" VALUES

Programmable values may be individually programmed
at start-up or any time thereafter. For ease of program-
ming, once the type of refrigerant is programmed in un-
der the Program key, a "defaults password" may be pro-
grammed to automatically program default values into
memory. This will preset all programmable values un-
der the Program key to values that will allow operation
of the chiller under most operating conditions. This al-
lows quick start-up programming for typical chilled wa-
ter applications.
To program the default values into memory, first press
the PROGRAM key followed by the ENTER key, to
program the "refrigerant type." Press the Program key
YORK INTERNATIONAL
1
L E A D
2
L E A D
R E S T A R T
again, key in the numbers "6140", then press Enter.
Asthe code is being keyed in, the digits are not dis-
played but are shown as "*" as shown:
P R O G R A M
M O D E
* * * *
When the Enter key is pressed, the following message
will appear:
D E F A U L T
S E T P O I N T S
1
=
Y E S ,
0
Key in a "1" for if default setpoints are required, or a
"0" for individually programmed values, then press En-
ter to store the selection into memory.
If individual programming is selected, the display will
now return to the Status display. If a default setpoints
have been selected, the display will momentarily dis-
play the message shown below before returning to the
Status display:
P R O G R A M
O P T I O N S
T O
D E F A U L T
It is often easier to select Default Set-
points and then reprogram a few that
require changing rather than pro-
gramming each individual value from
scratch.
A list of the default values entered into memory, if this
program option is selected, is shown below:
Programmable Value
Discharge Pressure Cutout
Low Ambient Cuout
High Ambient Temperature Cutout
Discharge Pressure Unload
High Motor Current Unload
Anti-Recycle Timer
Leaving Chilled Liquid Temp Cutout
Suction Pressure Cutout
FORM 201.18-NM8
?
=
N O,
1
S E T
V A L U E S
6140
Default
Setting
R-22
(28 bar) 399 PSIG
Std. Amb.
-4°C
25°F
Low Amb.
-4°C
25°F
38°C
130°F
R-22
26 bar 375 PSIG
100%
600 sec.
2°C
36°F
R-22
3 bar 44 PSIG
143
9