Print Key; Operating Data Printout - York YCAL0012EC Installation Operation & Maintenance

Air-cooled liquid chillers hermetic scroll
Hide thumbs Also See for YCAL0012EC:
Table of Contents

Advertisement

Unit Controls

PRINT Key

The PRINT key allows the operator to obtain a printout
of real-time system operating data or a history printout
of system data at the "instant of the fault" on the last six
faults which occurred on the unit. An optional printer is
required for the printout.

OPERATING DATA PRINTOUT

Pressing the PRINT key and then OPER DATA key al-
lows the operator to obtain a printout of current system
operating parameters. When the OPER DATA key is
pressed, a snapshot will be taken of system operating
conditions and panel programming selections. This data
will be temporarily stored in memory and transmission
of this data will begin to the printer. A sample Operating
Data printout is shown below. (Note: Not all values are
printed for all models.)
YORK INTERNATIONAL CORPORATION
MILLENNIUM LIQUID CHILLER
UNIT STATUS
2:04PM 01 JAN 05
SYS 1
SYS 2
COMPRESSORS RUNNING 2
OPTIONS
CHILLED LIQUID
AMBIENT CONTROL
LOCAL/REMOTE MODE
CONTROL MODE
LEAD/LAG CONTROL
FAN CONTROL
CURRENT FEEDBACK
SOFT START
EXPANSION VALVE
STATIC
PROGRAM VALUES
DSCH PRESS CUTOUT
SUCT PRESS CUTOUT
LOW AMBIENT CUTOUT
LEAVING LIQUID CUTOUT
ANTI RECYCLE TIME
FAN CONTROL ON PRESS
FAN DIFF OFF PRESS
NUMBER OF COMPRESSORS
NUMBER OF FANS PER SYSTEM
4
UNIT TRIP VOLTS
3.0
REFRIGERANT TYPE
REMOTE UNIT ID PROGRAMMED
UNIT DATA
RETURN LIQUID TEMP
104
NO COOLING LOAD
WATER
STANDARD
REMOTE
LEAVING LIQUID
AUTOMATIC
AMB & DSCH PRESS
NONE
ENABLED
THERMO-
395 PSIG
44 PSIG
25.0
DEGF
36.0
DEGF
600 SECS
240 PSIG
80 PSIG
6
R-22
2
58.2
DEGF
LEAVING LIQUID TEMP
COOLING RANGE
42.0 +/- 2.0 DEGF
AMBIENT AIR TEMP
LEAD SYSTEM
EVAPORATOR PUMP
EVAPORATOR HEATER
ACTIVE REMOTE CONTROL
UNIT
XXX.X AMPS
SOFTWARE VERSION
SYSTEM 1 DATA
COMP STATUS
1=OFF 2=OFF 3=OFF
RUN TIME
0- 0- 0- 0 D-H-M-S
SUCTION PRESSURE
DISCHARGE PRESSURE
SUCTION TEMPERATURE
SAT SUCTION TEMP
SUCTION SUPERHEAT
COOLER INLET REFRIG
LIQUID LINE SOLENOID
HOT GAS BYPASS VALVE
CONDENSER FAN STAGES
EEV OUTPUT
SYSTEM
XXX.X AMPS X.X VOLTS
DAILY SCHEDULE
S M T W T F S
MON START=00:00AM
STOP=00:00AM
TUE START=00:00AM
STOP=00:00AM
WED START=00:00AM
STOP=00:00AM
THU START=00:00AM
STOP=00:00AM
FRI START=00:00AM
STOP=00:00AM
SAT START=00:00AM
STOP=00:00AM
HOL START=00:00AM
STOP=00:00AM
See Service And Troubleshooting section
for Printer Installation information.
FORM 150.66-NM2 (906)
53.0
DEGF
74.8 DEGF
SYS 2
ON
OFF
NONE
X.X VOLTS
C.MMC.03.03
66 PSIG
219 PSIG
52.8 DEGF
40.0 DEGF
12.8 DEGF
31.6 DEGF
OFF
OFF
OFF
0.0 %
*=HOLIDAY
JOHNSON CONTROLS