R7999C CONTROLINKS™ CONTROLLER
Safety Features
• Class C operating software system.
• Fail-safe feedback potentiometer circuitry.
• Curve verification algorithms.
• Step size enforcement during commissioning.
• Point plausibility algorithms.
• Password protected.
• Weld-resistant algorithm for LCI-LCO contact set.
• Dual time base.
• Built-in self-test and safety relay circuits.
• Component anti-swap protection.
• Off curve checking algorithm.
• 1 million cycle count.
• 250,000 hour count.
SPECIFICATIONS
Model:
R7999C ControLinks™ Controller, consisting of a
four-channel actuator drive Input/Output (I/O) and
hardware interface for a variety of burner controllers.
Electrical Ratings:
Input Power:
R7999C: 100 to 120 Vac (+10/-15%), 50/60 Hz
(±10%), 10VA maximum.
Outputs:
Limit/Control OUT (LCO):
R7999C: 120 Vac, 8.0A run, 42A inrush (UL).
R7999C: 120 Vac, 6.0A run; 26A inrush.
Alarm (ALR):
R7999C: 120 Vac, 1A pilot duty (UL).
R7999C: 120 Vac, 1.0A at PF = 0.4, 6A inrush.
High Fire (HFP):
R7999C: 120 Vac, 1A pilot duty (UL)
R7999C: 120 Vac, 1A at PF = 0.4, 6A inrush.
Light-Off Position:
R7999C: 120 Vac, 1A pilot duty (UL)
R7999C: 120 Vac, 1A at PF = 0.4, 6 A inrush.

ORDERING INFORMATION

When purchasing replacement and modernization products from your TRADELINE® wholesaler or distributor, refer to the
TRADELINE® Catalog or price sheets for complete ordering number. If you have additional questions, need further
information, or would like to comment on our products or services, please write or phone:
1. Your local Honeywell Environmental and Combustion Controls Sales Office (check white pages of your phone
directory).
2. Honeywell Customer Care
1985 Douglas Drive North
Golden Valley, Minnesota 55422-4386
3. http://customer.honeywell.com or http://customer.honeywell.ca
International Sales and Service Offices in all principal cities of the world. Manufacturing in Belgium, Canada, China,
Czech Republic, Germany, Hungary, Italy, Mexico, Netherlands, United Kingdom, and United States.
32-00081EF—01
A-1, F1-1, F2-1, FG-1:
Source: 4.25 to 5.25V minimum at 5 mA
(counterclockwise [CCW] drive command).
Sinking: 0 to 0.6V maximum at -5 mA
(Clockwise [CW] drive command).
A-2, F1-2, F2-2, FG-2:
Source: 4.25 to 5.25V minimum at 5 mA
(Clockwise [CW] drive command).
Sinking: 0 to 0.6V maximum at -5 mA
(Counterclockwise [CCW] drive command).
Inputs:
Limit/Control In (LCI)
R7999C: 120 Vac, 8A run, 42A inrush (UL).
R7999C: 120 Vac, 6A run, 26A inrush.
Fuel 1 Select (FS1):
R7999C: 120 Vac at 2 mA (UL).
Fuel 2 Select (FS2)
R7999C: 120 Vac at 2 mA (UL).
Remote Reset (RR): 5V at 5 mA.
Feedback Potentiometer input (per channel):
CW: 5 Vdc at 1 mA.
S: 5 Vdc at 1 mA.
CCW: 5 Vdc at 1 mA.
Environmental Ratings:
Temperature Range:
Ambient: -40°F to +140°F (-40°C to +60°C).
Storage: -40°F to +150°F (-40°C to +65°C).
Humidity:
5 to 95 percent relative humidity, noncondensing.
Vibration:
0.0 to 0.5g continuous (V2 level).
Mounting: Mounts on Q7999 Universal Wiring Subbase.
Enclosure: NEMA1/IP40.
Accessories: 32002515-001 Three-Pin Electrical Connec-
tor (RS-485).
DSP3981 Display Toolkit. Can be used for program-
ming ControLinks™ as well as monitoring. Includes
S7999D Touchscreen Display.
DSP3956 Toolkit including ZM7999 commissioning
software, computer cable, and USB to 485 converter.
2