6.3.2
Selecting cables
Take the following criteria into account when selecting the connecting cables:
● Rated current
● Rated voltage
● If required, service factor
● System-dependent conditions, such as ambient temperature, routing type, cable cross-
● Configuration notes
● Requirements according to IEC/EN 60204‑1
● Dimensioning for bundled cable routing, e.g. according to DIN VDE 0298 Part 4 or
6.3.3
Connecting the machine for a specific direction of rotation
If the machine has one shaft extension or two shaft extensions with different diameters, the
direction of rotation when looking at the front of the single or the thicker shaft extension is
defined as follows:
● If you connect the power cables in the phase sequence L1, L2, L3 to U, V, W, the resulting
● If you interchange two connections, e.g. L1, L2, L3 to W, V, U, the resulting rotation will be
● On machines which are only allowed to run in one direction, the rating plate shows an arrow
NOTICE
Incorrect direction of rotation
The machine will not be adequately cooled if it is operated other than how it was originally
ordered or with the incorrect direction of rotation. This can result in machine damage.
Observe the direction of rotation data on the nameplate.
SIMOTICS HT Series HT-direct 1FW4...1......A
Operating Instructions 11/2018
section as defined by required length of cable, etc.
IEC 60364-5-52
rotation will be clockwise.
counter-clockwise.
which indicates the permitted direction of rotation, and it also specifies the terminal
connections in the required phase sequence.