Error Codes When Performing A Test Run; Disposal - Daikin Sky Air Advance Series Installation Manual

Hide thumbs Also See for Sky Air Advance Series:
Table of Contents

Advertisement

6 Disposal

5.3
Error codes when performing a
test run
If the installation of the outdoor unit has NOT been done correctly,
the following error codes may be displayed on the user interface:
Error code
Nothing displayed
▪ The wiring is disconnected or there is a
wiring error (between power supply and
(the currently set
outdoor unit, between outdoor unit and
temperature is not
indoor units, between indoor unit and
displayed)
user interface).
▪ The fuse on the outdoor unit PCB has
blown out.
E3, E4 or L8
▪ The stop valves are closed.
▪ The air inlet or air outlet is blocked.
U1 or E7
There is a missing phase in case of three-
phase power supply units.
Note: Operation will be impossible. Turn
OFF the power, recheck the wiring, and
switch two of the three electrical wires.
L4
The air inlet or air outlet is blocked.
U0
The stop valves are closed.
U2
▪ There is a voltage imbalance.
▪ There is a missing phase in case of
three-phase power supply units. Note:
Operation will be impossible. Turn OFF
the power, recheck the wiring, and switch
two of the three electrical wires.
U4 or UF
The inter-unit branch wiring is not correct.
UA
The outdoor and indoor unit are
incompatible.
6
Disposal
This unit uses hydrofluorocarbon. Contact your dealer when
discarding this unit.
NOTICE
Do NOT try to dismantle the system yourself: dismantling
of the system, treatment of the refrigerant, oil and other
parts MUST comply with applicable legislation. Units
MUST be treated at a specialised treatment facility for
reuse, recycling and recovery.
Installation manual
16
Possible cause
RZA200+250D7Y1B
Sky Air Advance-series
4P573384-1 – 2019.04

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rza200d7y1bRza250d7y1b

Table of Contents