25 kw supplementary electric heater

Advertisement

STEP 11 - Replace Heater compartment panel on air
handler.

Section 6. Tables

Important: The BAYEV* electric heat accessory may include up to a combination of three 30 and/or 60 amp circuit break-
ers to provide an electrical disconnect for service personnel that is intended to help protect internal electrical components
in the event of a short circuit or ground fault. As designed, the circuit breakers supplied in the BAYEV* accessory DO NOT
provide overcurrent protection of the branch circuit. Therefore, the branch circuit(s) shall be sized and protected according
to the unit nameplate.
Heater Model No.
BAYEVCC25BK1AA
Table 6.2 MINIMUM HEATER AIRFLOW CFM - HEATER MATRIX
MODEL NO.
TAM7A0C48H41SB
TAM7A0C60H51SB
TAM7B0C60H51SA
TAMGA0C48H41SA
TAMGA0C60H51SA
TAM8A0C48H41CB
TAM8A0C60H51CB
TAM8B0C60H51CA
SEE AIR HANDLER NAMEPLATE OR PRODUCT DATA FOR EXCEPTIONS
1 Not approved for 208V when installed in horizontal left position without Heat Pump.
Table 6.1 BAYEV -- HEATER DATA
Number of
Capacity
Circuits
kW
3
24.00
BAYEACC25BK1AA
W/O HP / WITH HP
1625 -- 1813
1625 1 -- 1813
1625 -- 1813
1625 1 -- 1813
1625 -- 1813
1625 1 -- 1813
240 VOLT
Heater Amps
per Circuit
BTUH
82000
40/40/20
--
INSTALLER'S GUIDE
208 VOLT
Capacity
Heater Amps
per Circuit
kW
BTUH
18.00
61500
34.6/34.6/17.3