Supervisor Ii Control Parameters - Sullair DR13 125H Operator's Manual And Parts List

Industrial air compressor, 100-200 hp
Table of Contents

Advertisement

5.8 SUPERVISOR II CONTROL PARAMETERS-- DS-- 13
SENSOR
FUNCTION
P1
Interstage Air Pressure
P2
Discharge Air Pressure
P3
Oil Filter Outlet Pressure
P4
Oil Filter Inlet Pressure
Dp1
Inet Filter Vacuum
Dp2
Oil Filter Differential (P4---P3)
st
T1
1
Stage Discharge Air Temp.
nd
T2
2
Stage Discharge Air Temp.
T3
Oil Filter Outlet Temp.
nd
T4
2
Stage Inlet Air Temp.
T5
Aftercooler Discharge Temp.
UNITS
PREALARM
psig/bar
49/ 3.4
psig/bar
psig/bar
psig/bar
inches H
O
2
psig/bar
20/ 1.4
˚F/˚C
435/ 224
˚F/˚C
435/ 224
˚F/˚C
155/ 68
˚F/˚C
155/ 68
˚F/˚C
155/ 68
SUPERVISOR II
SHUTDOWN
52/ 3.6
N/A
50/ 3.4
N/A
25/ 1.7
N/A
N/A
15
N/A
N/A
445/ 229
445/ 229
160/ 71
160/ 71
160/ 71
Section 5
FAILURE
MODE
Hi
Lo
Lo
N/A
Hi
Hi
Hi
Hi
Hi
Hi
Hi
21

Hide quick links: