Selection of installation place
In case of continued operation of the indoor unit under
high-humidity conditions as described below, dew may
condense and water may drop.
Especially, high-humidity atmosphere (dew point
temperature : 23°C or more) may generate dew inside the
ceiling.
1. Unit is installed inside the ceiling with slated roof.
2. Unit is installed at a location using inside of the ceiling
as fresh air take-in path.
3. Kitchen
If installing a unit at such place, put insulating material
(glass wool, etc.) additionally on all the positions of the
indoor unit which come to contact with high-humidity
atmosphere.
Advice
Set a check service opening panel at right side of the unit
(size: 450 x 450mm or more) for piping, maintenance, and
servicing.
Ceiling height
Model RAV-
SM560UT-E, SM800UT-E
SM1100UT-E, SM1400UT-E
When the height of the ceiling exceeds the distance of the
item Standard/4-way in Table below, the hot air is difficult to
reach the floor. Therefore, it is necessary to change the
setup value of the high ceiling switch or discharge direction.
REQUIREMENT
• When using the air conditioner with 2-way discharge
system with the standard setting (at a shipment), it
may stop abnormally in heating. Therefore, change
the setting switch according to the number of
discharge direction and the ceiling height.
• When using the air conditioner with 2-way/3-way
discharge system, a strong wind blows directly if
the ceiling height is lower than the standard.
Therefore, change the setting switch according to
height of the ceiling.
• When using the high ceiling (1) or (2) with 4-way
discharge system, the draft is apt to be felt due to
drop of the discharge temperature.
Height list of ceiling possible to be installed
Model
RAV-
No. of discharge direction
Standard (at shipment)
High ceiling (1)
High ceiling (2)
Possible installed ceiling height
Up to 3.8 m
Up to 4.3 m
SM560UT-E
4-way
3-way
2-way
4-way
2.8
3.2
3.5
3.0
3.2
3.5
3.8
3.3
3.5
3.8
3.6
Discharge direction
As shown in the following figure, No. of
discharge directions can be selected according
to the shape of rooms and installation position.
RAV-SM560UT-E to RAV-SM1400UT-E
As shown in the following figure direction are
not acceptable.
RAV-SM560UT-E to RAV-SM1400UT-E
• To change discharge direction, use a shielding
plate.
• When attaching a shielding plate, remove the
ceiling panel and insert the shielding plate into
the discharge port as shown in the figure below.
Shielding plate
(Prepared locally)
Install the air conditioner certainly to sufficiently
withstand the weight.
If the strength is insufficient, the unit may fall
down resulting in human injury.
Perform a specified installation work to guard
against an earthquake.
An incomplete installation can cause accidents
by the units falling and dropping.
SM800UT-E
SM1100, SM1400UT-E
3-way
2-way
4-way
3.3
3.6
3.6
3.5
3.8
3.9
3.8
4.2
32
Refrigerant pipe side
WARNING
High ceiling setup
3-way
2-way
Set data
3.9
4.2
0000
4.1
4.3
0001
4.3
0003
(Unit : m)