[5-1 Dipswitch Functions and Factory Settings ]
(2) Additional dipswitch settings at time of shipment
Switch
SW4
1-10
SW6-10:
1:ON, 0:OFF
OFF
No.769
1000000011
No.817
1000110011
No.818
0100110011
No.832
0000001011
No.848
0000101011
No.891
1101111011
No.896
0000000111
No.897
1000000111
No.900
0010000111
No.912
0000100111
No.913
1000100111
No.915
1100100111
No.916
0010100111
No.918
0110100111
SW4
1-10
[0:OFF,
No.921
1001100111
1:ON]
(Note 1)
SW6-10:ON
No.922
0101100111
No.932
0010010111
No.933
1010010111
No.934
0110010111
No.964
0010001111
No.968
0001001111
No.972
0011001111
No.974
0111001111
No.982
0110101111
No.988
0011101111
No.997
1010011111
No.1006
0111011111
4
- chapter 5
Function according to switch setting
Function
OFF (LED3 Unlit)
Self-diagnosis/operation
monitor
Test run mode: ON/OFF
Stops all ICs
Starts up drive recorder
Enabled
Data collection during an
Disabled
error
Cumulative compressor
Retained
operation time deletion
Continuous heating cycle
Disabled
function
Smooth auto-shift startup
mode during startup of
Disabled
heating operation
OC
Retained (IC/OC)
Clearance of error
history
OS
Retained (OS)
Depends on the combined setting with No.
High sensible heat opera-
900 (Note 4)
tion setting
(Factory setting: OFF)
Depends on the combined setting with No.
High sensible heat opera-
897 (Note 4)
tion setting
(Factory setting: OFF)
Pump down function
Normal control
Forced defrost (Note 3)
Normal control
Defrost start temperature
HP72 - HP120:
(Note 3)
-11°C [12°F]
Defrost end temperature
HP72 - HP120:
(Note 3)
7°C [45°F]
Changes the defrost timer
50 minutes
setting (Note 3)
Temperature/pressure unit
2
°C/kgf/cm
selection
Refrigerant amount adjust-
Normal control
ment
Heating backup
Disabled
Effective only when
TH7 5 is true or the
Snow sensor setting
snow sensor contact
input is on.
Continuous fan op-
Snow sensor setting
eration (FAN=50%)
Depends on the setting combination with No.
Target evaporation tem-
982 (Note 5)
perature setting
(Factory setting: OFF)
Target condensation tem-
perature setting
Disabled
(Tcm max=53°C [126°F])
Automatic cooling/heating
mode (IC with the smallest
Normal control
address)
Panel heater output
Enabled
Depends on the setting combination with No.
Target evaporation tem-
964 (Note 5)
perature setting
(Factory setting: OFF)
Refrigerant recovery/Evac-
uation (LEV2, LEV1, SV2
Disabled
open)
Multiple-stage low-noise
See note 8 below.
setting
(Factory setting: OFF)
Switch setting timing
ON (LED3 Lit)
Anytime after power on
Sends a test-run sig-
Anytime after power on
nal to all IC
Disabled
Anytime after power on
Enabled
Anytime after power on
Any time after being energized (When
Cleared
changed from OFF to ON)
After being energized and while the com-
Enabled
pressor is stopped
After being energized and while the com-
Enabled
pressor is stopped
Deleted (IC/OC)
Anytime after power on (OFF ON)
Deleted (OS)
After being energized and while the com-
pressor is stopped
After being energized and while the com-
pressor is stopped
Pump down opera-
After being energized and while the com-
tion
pressor is stopped
Anytime after power on
10 minutes after the completion of de-
Forced defrost starts
frost operation (OFF ON) or 10 minutes
after compressor start-up (OFF ON)
-8°C [18°F]
Anytime after power on
5°C [41°F]
Anytime after power on
90 minutes
Anytime after power on (OFF ON)
°F/psi
Anytime after power on
Anytime after power on (except during
Refrigerant amount
initial startup/becomes ineffective 90
adjust mode
minutes after compressor started up.)
Enabled
Anytime after power on
Effective when TH7
Anytime after power on
5 is true
Intermittent fan op-
eration (The fan op-
erates in the cycle of
being in operation at
100% capacity for 5
Anytime after power on
minutes and then
stops and remains
stopped for 30 min-
utes.)
Anytime after power on
Enabled
Anytime after power on
Automatic cooling/
Before power on (After configuring the
heating mode
setting, perform a power reset.)
After being energized and while the com-
Disabled
pressor is stopped
Anytime after power on
After being energized and when units are
Enabled
stopped
After power on and while the compressor
is stopped
Units that
require
switch
setting
(Note 2)
C
A
A
A
C
B
A
C
A
A
A
D
B
B
B
C
A
A
C
C
A
A
A
D
A
C
A
HWE18240_GB