[2-4 M-NET Address Settings ]
(1) CN51
Distant control
Relay circuit
board
L
X
1
Y
L
2
Preparations
in the field
L1 : Outdoor unit error display lamp
L2 : Compressor operation lamp (compressor running state)
X, Y : Relay (coil =<0.9W : DC12V)
1. Optional part : PAC-SC37SA-E or field supply.
3. When using a base heater, error output will not be available.
(3) CN3N
External input
Relay circuit
adapter
X
1
2
Y
3
Preparations
Maximum cable
in the field
length is 10m
(4) CN3D
External input
Relay circuit
adapter
X
Y
Preparations
in the field
Maximum cable
length is 10m
X : Low-noise mode
Y : Compressor ON/OFF
X,Y : Relay Contact rating voltage >= DC15V
Contact rating current >= 0.1A
Minimum appicable load =< 1mA at DC
2. Optional part : PAC-SC36NA-E or field supply.
(5) CN3K
External input
Relay circuit
adapter
X
Preparations
in the field
Maximum cable
length is 10m
X : Energy-saving mode command
X : Relay
Contact rating voltage >= DC15V
Contact rating current >= 0.1A
Minimum appicable load =< 1mA at DC
2. Optional part : PAC-SC36NA-E or field supply.
8
- chapter 2
External input
adapter
1 Outdoor unit
control board
CN51
X
Y
5
4
3
Maximum cable
length is 10m
3
2
Outdoor unit
control board
CN3N
OFF
Y
ON
Cooling
X : Cooling / Heating
Y : Validity / Invalidity of X
X,Y : Relay
Contact rating voltage >= DC15V
Contact rating current >= 0.1A
Minimum applicable load =< 1mA at DC
2. Optional part : PAC-SC36NA-E or field supply.
Outdoor unit
2
control board
CN3D
1
2
3
Outdoor unit
2
control board
CN3K
1
2
3
(2) CN3S
External input
Relay circuit
adapter
1
X
2
3
Preparations
in the field
Maximum cable
length is 10m
X : Relay
Contact rating voltage >= DC15V
Contact rating current >= 0.1A
Minimum applicable load =< 1mA at DC
Snow sensor : The outdoor fan runs when X is closed
in stop mode or thermostat mode.
2. Optional part : PAC-SC36NA-E or field supply.
X
OFF
ON
Normal
Heating
External input
Relay circuit
adapter
1
X
2
3
Preparations
in the field
Maximum cable
length is 10m
X : Low-noise mode
X : Relay
Contact rating voltage >= DC15V
Contact rating current >= 0.1A
Minimum applicable load =< 1mA at DC
2. Optional part : PAC-SC36NA-E or field supply.
Low-noise mode : The noise level is reduced by controlling the maximum
fan frequency and maximum compressor frequency.
Outdoor unit
2
control board
CN3S
Outdoor unit
2
control board
CN3D
HWE18240_GB