Abbreviation
SHAOUT
SHared (virtual) Analog OUTput module
SHBIN
SHared (virtual) Binary INput module
SHBOUT
SHared (virtual) Binary OUTput module
Soft load
Generator soft loading according to Load ramp loop setting
Soft unload
Generator soft unloading according to Load ramp loop setting
SPI
Single Parallel Island application - for single gensets in parallel with mains or in
island operation; suitable for CHP applications; no MCB control
SPM
Single Prime Mover application - for single gensets without mains
SPN
Suspect Parameter Number (see SAE J1939-71)
SPtM
Single Parallel to Mains application - for single gensets in parallel with mains or in island operation,
with AMF support; both MCB and GCB controlled
SSB
Single Stand-By application - for single gensets with mains and break transfer to
mains
VPIO
Virtual periphery I/O module – internal "SW wires" linking binary outputs to inputs
controllers via inter-controller CAN2
VS
VAr Sharing - ensures VAr sharing between gensets on site via the CAN2 bus (for island parallel or
mains parallel operation of multiple gen-sets)
VT
Voltage Transformer
#
Setting of setpoints (with this character in front of them) is shared between controllers controllers via
inter-controller CAN2
NT
Alarm/History
Record
ECU
SHAinCfgErr
ECUDiagBlocked
Wrong config
35319 C
Table 7 - Digital Controller Alarm Abbreviations
Table 8 - Digital Controller List of Alarms
Indication of error in communication with ECU.
Check if the ECU is:
- correctly connected to the CAN1 port of the controller (see ComAp Electronic Engines
Support manual for information about ECU connection)
- powered up
- terminating resistors are properly connected
- the CAN bus Low and High wires are not swapped
Shared Analog module configuration error – i.e. more than one source module
(SHAOUT) were configured (on the CAN2 bus). Make sure that only one SHAOUT x
module is configured in controllers.
Alarm is active when Comms settings: ECU diag = DISABLED. This setting means that
ECU alarms are not displayed and considered by controller and this alarm is the setting
notification.
Wrong controller configuration indication.
Indicates that controller hardware doesn't support PLC used in configuration. To check it
send the IDch and Dngl strings3 from controller Info screen 2 and archive to your techni-
cal support.
MGG155/210 Operating Manual
Description
Description
Troubleshooting
45